| 2017-10-02 14:17:57 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN STATES THAT THIS IS A 90% SUBMITTAL NOT FOR | | | CONSTRUCTION. PLEASE SUBMIT PLANS THAT ARE FOR | | | CONTRUCTION AND/OR REMOVE THAT STATEMENT. FBC 107.2.1, | | | 107.4, 107.5 | | | 2. PROVIDE AIC RATING OF SERVICE EQUIPMENT. NEC 110.3, | | | 110.9 | | | 3. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT SERVICE TO CONFIRM AIC RATING IS ADEQUATE. | | | NEC 110.10 | | | 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE ALL | | | LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC | | | 215.2, 220, 408.30 | | | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. NEC 250.94 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|