| Plan Review Notes For Permit 17090359 |
| Permit Number |
17090359 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-22 07:05:10 | 1) SUBMIT A LISTED FIRESTOPPING DETAIL FOR THE FLOOR | | | PENETRATION OF THE RELOCATED RAIN WATER LEADER. SHOW | | | THE FIRE RATING OF THE EXISTING FLOOR ON THE PLAN. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 2) THE RECOMMENDATIONS FROM WOJCIESZAK & ASSOCIATES | | | REFERS TO PLUGGING THE EXISTING ROOF DRAIN FOR THE | | | EXISTING RAIN WATER LEADER BUT THERE IS NO MENTION OF | | | RECONNECTING THIS ROOF DRAIN. THIS ROOF DRAIN CANNOT BE | | | ABANDONED. CLARIFY WHAT WILL BE DONE WITH THIS ROOF | | | DRAIN IN THE REPORT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|