| 2017-10-12 08:13:48 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | THE ELECTRICAL RISERS PROVIDED ARE NOT CLEAR AS TO |
| | FUNCTION AND LACK INFORMATION. FURTHER PLAN REVIEW |
| | COMMENTS ARE POSSIBLE. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR ATS-1 AND ATS-2 TO |
| | CONFIRM CAPACITY OF GENERATOR IS SUFFICIENT FOR THE |
| | ADDITIONAL LOAD FROM ATS-2. IT APPEARS THAT ATS-1 IS |
| | ALSO FEEDING THE FIRE PUMP? IF THIS IS THE CASE, IS THE |
| | TRANSFER SWITCH RATED FOR FIRE PUMP USE? GENERATOR MUST |
| | HAVE CAPACITY FOR THE LOCKED ROTOR CURRENT OF THE FIRE |
| | PUMP IN ADDITION TO ALL OTHER LOADS. PROVIDE COMPLETE |
| | LOAD CALCULATION. ALSO NEED FURTHER INFORMATION ON FIRE |
| | PUMP FEED, WHICH SHOULD NOT BE FED FROM A PANEL THAT |
| | FEEDS OTHER LOADS. NEC 700.4, 702.4(B)(2), 695.4(A), |
| | 695.4(B)(3). FBC 107.2.1 |
| | 2. IS ATS-1 BEING FED FROM TWO 1200 AMP PANELS AND THEN |
| | FEEDING ANOTHER 1200 AMP PANEL WITH A 600 AMP FEED? OR |
| | IS IT THE OTHER WAY AROUND? PROVIDE CLARIFICATION. FBC |
| | 107.2.1 |
| | 3. SHOW FEEDER CONDUIT AND WIRE SIZE TO ATS-1 FROM |
| | GENERATOR. FBC 107.2.1; NEC 310.15(B)(16) |
| | 4. WHY IS THE EMERGENCY FEED TO ATS-2, WHICH IS 200 |
| | AMP, ONLY SIZED AT 60 AMP? IS THE BREAKER FROM THE |
| | NORMAL SOURCE A 200 AMP OR A 150 AMP? WIRE SIZE STATED |
| | AS 2/0 IS NOT RATED FOR 200 AMP. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. FBC 107.2.1; NEC 310.15(B)(16) |
| | 5. PROVIDE COPY OF CONTRACT WITH SCOPE OF WORK AND |
| | VALUE OF WORK LISTED. FBC 109.3 |
| | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 7. PROVIDE AIC RATING OF EACH ATS. INDICATE ON SPEC |
| | SHEETS WHICH MODEL IS BEING INSTALLED. NEC 110.3, 110.9 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |