Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop B
Sequence Number 3
Notes
Date Text
2018-03-17 16:46:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-14. OK
  
 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN
 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN
 RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE
 DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC
 A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A
 PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION
 REQUIRED SUBJECT TO INSPECTOR'S DISCRETION.
  
 3RD REVIEW, DETAILS WERE PROVIDED. 03-S1 IS NOT CLEAR
 AS TO COMPLIANCE AS IT LACKS DIMENSIONS. 02-S1 LACKS
 THE KNEE AND TOE CLEARANCE REQUIRED BY FBC A 306.
  
 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC
 A 227 (CHECK OUT AISLE).
  
 3RD REVIEW, SEE ITEM 15. DETAILS PROVIDED EITHER ARE
 NOT CLEAR AS TO COMPLIANCE (03-S1) OR IS NOT COMPLIANCE
 (02-S1). ALTHOUGH IT IS UNDERSTOOD THAT MILLWORK WILL
 BE CUSTOM, THE PLANS SHOULD SET FORTH THE DESIGN
 CRITERIA FOR CODE COMPLIANCE.
  
 17-22. OK
  
 23. SEE FS 553.80(2)(B). DUE TO THE NUMEROUS COMMENTS
 FROM MULTIPLE TRADES, PRIOR TO RESUBMITTAL APPLICANT
 (CONTRACTOR IS SUGGESTED) IS TO REVIEW COMMENTS AND
 PLANS, CONFIRM ALL COMMENTS HAVE BEEN ADDRESSED, AND
 SCHEDULE A PRE-RESUBMITTAL MEETING.
  
 24. OK
  
 NEW COMMENT 3RD REVIEW:
  
 25. EXPLAIN THE DISCREPANCY BETWEEN PROPERTY APPRAISER
 BUILDING TOTAL SF AREA OF 10,161 AND THE SF AREA SHOWN
 ON LS-1, BUILDING AREA & HEIGHT CALCULATION, 6313. IS
 THERE A FIRE WALL, REQUIRED TO BE 3 HOURS, WHICH MEETS
 ALL REQUIREMENTS TO BE ABLE TO CONSIDER THE TWO AREAS
 TWO SEPARATE BUILDINGS? IF YES, REVISE THE PLAN TO
 CLARIFY. IF NO, THE AREA CALCULATIONS ARE NOT CORRECT
 AS THEY CONSIDER ONLY A PORTION OF THE BUILDING. SEE
 FBC CHAPTER 5.
 *******************************************************
 **************
 INTERNAL USE ONLY:
 USC-404 TYPE 437 - ALT:NON-RES,NON-HSKPG
 SQUARE FEET - 6313
  
 CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B
 UNITS: 1
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 6313
 SQ FT FOOTPRINT: 6313
 SQ FT ROOF: 6313
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: RUM DISTILLERY/TASTING TOURS/MERCANTILE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED F1,M
  
  
  