| 2018-03-17 16:46:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1-14. OK |
| | |
| | 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN |
| | 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW |
| | COMPLIANCE WITH FBC A 902.3. |
| | |
| | PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW |
| | COMPLIANCE WITH FBC A 902.3. |
| | |
| | 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN |
| | RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE |
| | DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC |
| | A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A |
| | PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION |
| | REQUIRED SUBJECT TO INSPECTOR'S DISCRETION. |
| | |
| | 3RD REVIEW, DETAILS WERE PROVIDED. 03-S1 IS NOT CLEAR |
| | AS TO COMPLIANCE AS IT LACKS DIMENSIONS. 02-S1 LACKS |
| | THE KNEE AND TOE CLEARANCE REQUIRED BY FBC A 306. |
| | |
| | 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC |
| | A 227 (CHECK OUT AISLE). |
| | |
| | 3RD REVIEW, SEE ITEM 15. DETAILS PROVIDED EITHER ARE |
| | NOT CLEAR AS TO COMPLIANCE (03-S1) OR IS NOT COMPLIANCE |
| | (02-S1). ALTHOUGH IT IS UNDERSTOOD THAT MILLWORK WILL |
| | BE CUSTOM, THE PLANS SHOULD SET FORTH THE DESIGN |
| | CRITERIA FOR CODE COMPLIANCE. |
| | |
| | 17-22. OK |
| | |
| | 23. SEE FS 553.80(2)(B). DUE TO THE NUMEROUS COMMENTS |
| | FROM MULTIPLE TRADES, PRIOR TO RESUBMITTAL APPLICANT |
| | (CONTRACTOR IS SUGGESTED) IS TO REVIEW COMMENTS AND |
| | PLANS, CONFIRM ALL COMMENTS HAVE BEEN ADDRESSED, AND |
| | SCHEDULE A PRE-RESUBMITTAL MEETING. |
| | |
| | 24. OK |
| | |
| | NEW COMMENT 3RD REVIEW: |
| | |
| | 25. EXPLAIN THE DISCREPANCY BETWEEN PROPERTY APPRAISER |
| | BUILDING TOTAL SF AREA OF 10,161 AND THE SF AREA SHOWN |
| | ON LS-1, BUILDING AREA & HEIGHT CALCULATION, 6313. IS |
| | THERE A FIRE WALL, REQUIRED TO BE 3 HOURS, WHICH MEETS |
| | ALL REQUIREMENTS TO BE ABLE TO CONSIDER THE TWO AREAS |
| | TWO SEPARATE BUILDINGS? IF YES, REVISE THE PLAN TO |
| | CLARIFY. IF NO, THE AREA CALCULATIONS ARE NOT CORRECT |
| | AS THEY CONSIDER ONLY A PORTION OF THE BUILDING. SEE |
| | FBC CHAPTER 5. |
| | ******************************************************* |
| | ************** |
| | INTERNAL USE ONLY: |
| | USC-404 TYPE 437 - ALT:NON-RES,NON-HSKPG |
| | SQUARE FEET - 6313 |
| | |
| | CONSTRUCTION TYPE: 14-III-B - 5TH ED TYPE III-B |
| | UNITS: 1 |
| | FLOORS: 1 |
| | BEDROOMS: |
| | ROOMS: |
| | SQ FT LIVABLE: 6313 |
| | SQ FT FOOTPRINT: 6313 |
| | SQ FT ROOF: 6313 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: |
| | PROP USE: RUM DISTILLERY/TASTING TOURS/MERCANTILE |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: |
| | |
| | BLDG CODE: FL 2014 |
| | OCC CLASS: 5TH ED F1,M |
| | |
| | |
| | |