| Plan Review Notes For Permit 17090272 |
| Permit Number |
17090272 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-01-08 10:07:24 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SHT. M-1 KEYNOTE #13 CALLS OUT A 4" CONCENTRIC VENT | | | PROVIDE DETAIL SHOW TYPE OF PIPE LENGTH AND | | | CONFIGURATION. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. SHT. M2 BOILER VENT DETAIL SHOWS 3 DIFFERENT | | | CONFIGURATION PLEASE PROVIDE A SITE SPECIFIC DRAWING | | | WITH PIPE TYPE, SIZING AND LENGTH. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. SHT. P-2 SHOW 2 DIFFERENT VENT CONFIGURATIONS PLEASE | | | PROVIDE A SITE SPECIFIC DRAWING WITH PIPE TYPE, SIZING | | | AND LENGTH. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. SHT. G-1 HEATER DETAIL SHOWS A DUAL PIPE INLET | | | OUTLET VENT CONFIGURATION SHT. P-2 SHOWS I SINGLE | | | CONCENTRIC VENT PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 5. THE TANKLESS HEATER MANUFACTURE SPECIFICATION | | | INSTALLATION MANUAL IS NOT COMPLETE PLEASE PROVIDE | | | COMPLETE MANUAL. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|