Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-12-12 14:29:171615 CLARE AVENUE
 PERMIT #17090272
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT - PROVIDE TACTILE SIGNAGE AT ALL
 REQUIRED EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT - PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]