Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop B
Sequence Number 2
Notes
Date Text
2018-01-04 17:07:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE PREVIOUS COMMENT. PLAN COMPLIES AS A
 "SUBSTANTIAL IMPROVEMENT". HOWEVER, RESPONSE LETTER
 STATES THAT THIS IS NOT A SUBSTANTIAL IMPROVEMENT DUE
 TO REDUCTION OF SCOPE AND THAT A COST BREAKDOWN WOULD
 BE PROVIDED. THIS WAS NOT PROVIDED.
  
 THIS COMMENT MAY BE DISREGARDED IF APPLICANT DOES NOT
 OBJECT TO "SUBSTANTIAL IMPROVEMENT" DETERMINATION.
  
 2-7. OK
  
 8. FBC EB 301.1, THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY (CH 10). A CURSORY LOOK INTO RECORDS FOR THIS
 BUILDING APPEAR TO REFLECT THAT CURRENT OCCUPANCY IS
 BUSINESS OR STORAGE. IF THIS IS A CHANGE OF OCCUPANCY,
 REVISE PLAN TO NOTE THE CHANGE OF OCCUPANCY FROM
 CURRENT OCCUPANCY TO MIXED OCCUPANCY F1, M, AND
 POSSIBLE ANOTHER OCCUPANCY (TASTING/TOURS).
  
 2ND REVIEW, RESPONSE STATES THAT THIS IS A CHANGE OF
 OCCUPANCY FROM BUSINESS TO F1, AND PLANS HAVE BEEN
 REVISED TO STATE SUCH, THEN RESPONSE MAKES SOME
 STATEMENTS REGARDING COMPLIANCE. I WAS UNABLE TO
 LOCATION THE INFORMATION WHICH STATES THAT THIS IS
 CURRENTLY BUSINESS, PROPOSED F1 WITH ACCESSORY
 MERCANTILE; IF THIS IS ON THE PLAN AS STATED, PLEASE
 PROVIDE THE PAGE NUMBER AND THIS COMMENT WILL BE
 REMOVED.
  
 9-13. OK
  
 14. S4, A DASHED LINE (3') AT THE ENTRY DOOR IS SHOWN.
 CLARIFY WHAT THIS IS. REVISE PLAN TO SHOW ACCESSIBLE
 ROUTE AT ENTRY DOOR WHICH COMPLIES WITH FBC A 303.2
 (SEE ALSO FBC A 202.3).
  
 2ND REVIEW, I WAS UNABLE TO LOCATE THE NOTE SHOWING
 COMPLIANCE WITH THE REQUIREMENT FOR AN ACCESSIBLE
 ENTRY, PLEASE ADVISE.
  
 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN
 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN
 RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE
 DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC
 A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A
 PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION
 REQUIRED SUBJECT TO INSPECTOR'S DISCRETION.
  
 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC
 A 227 (CHECK OUT AISLE).
  
 2ND REVIEW, THE TWO COUNTERS LABELED PN25 HAVE BEEN
 RENUMBERED. RESPONSE LETTER DID NOT INDICATE WHERE
 DETAILS FOR THE COUNTERS SHOWING COMPLIANCE WITH FBC
 A902.3 CAN BE FOUND. EITHER ADVISE, OR REQUEST A
 PROVISO: COMPLIANCE WITH FBC A902.3 REQUIRED, REVISION
 REQUIRED SUBJECT TO INSPECTOR'S DISCRETION.
  
 17. NO FIRE SPRINKLER INFORMATION PROVIDED. EITHER
 PROVIDE A PLAN OR INCORPORATE ALL REQUIREMENTS OF FBC B
 404.6 EXCEPTION INTO THE PLAN.
  
 2ND REVIEW, RESPONSE STATES: THE FIRE SPRINKLER DESIGN
 AND DRAWINGS ARE PROVIDED VIA SEPARATE PERMIT BY A
 SPECIALTY ENGINEER ..."
  
 SEE FIRE COMMENTS AND FBC 107.3.5.1.1(5). ALTHOUGH THE
 MEZZANINE EXCEPTION IS NOT LONGER APPLICABLE, FIRE
 SUPPRESSION INFORMATION TO BE INCORPORATED INTO THE
 PLAN PRIOR TO PERMIT ISSUANCE. SEE FIRE COMMENTS; IT IS
 ACKNOWLEDGED THAT THE FIRE SHOP DRAWINGS AND PERMIT MAY
 BE SUBMITTED AFTER PERMIT ISSUANCE. IF FIRE'S COMMENT
 IS NOT CLEAR AS TO WHAT IS REQUIRED WITH THIS BUILDING
 PERMIT SUBMITTAL, PLEASE CONTACT THE FIRE REVIEWER FOR
 CLARIFICATION.
  
 18. OK
  
 19. LS2, TRAVEL DISTANCE IS SHOWN AS 94' TO THE BASE OF
 THE STAIR. SEE FBC B 1016.3, EXIT ACCESS TRAVEL
 DISTANCE IS TO BE MEASURED FROM THE MOST REMOTE POINT
 WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH
 OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT. IT APPEARS THAT THE MEASUREMENT IS
 TO THE BASE OF THE STAIR, AT WHICH POINT OCCUPANT IS
 REQUIRED TO GO THROUGH THE FIRST FLOOR TO REACH AN
 EXIT, PLEASE REVISE OR CLARIFY. SEE ALSO FBC B 404.9
 (<200' TRAVEL DISTANCE).
  
 20. FBC 107, PALLET RACKS, REVISE PLAN TO INCLUDE
 HEIGHT LIMITATION.
  
 RESPONSE LETTER STATES THAT THIS IS PREDICATED UPON THE
 TYPE(S) OF FIRE SPRINKLERS SPECIFIED AND IS TYPICALLY
 PROVIDED BY THE FIRE SPRINKLER SPECIALTY ENGINEER.
 REVIEW OF THIS ITEM WILL BE DONE WHEN FIRE SPRINKLER
 INFORMATION REQUIRED BY FIRE IS PROVIDED.
  
 21-22. OK
  
 NEW COMMENTS:
  
 23. SEE FS 553.80(2)(B). DUE TO THE NUMEROUS COMMENTS
 FROM MULTIPLE TRADES, PRIOR TO RESUBMITTAL APPLICANT
 (CONTRACTOR IS SUGGESTED) IS TO REVIEW COMMENTS AND
 PLANS, CONFIRM ALL COMMENTS HAVE BEEN ADDRESSED, AND
 SCHEDULE A PRE-RESUBMITTAL MEETING.
  
 24. ADVISORY ONLY - PRODUCT APPROVALS WERE SUBMITTED.
 PLEASE BE ADVISED THAT THIS IS OPTIONAL AT THIS TIME.
 THIS MAY, UPON REQUEST, BE A DEFERRED SUBMITTAL AND MAY
 BE SUBMITTED, NO FEE, TO BE REVIEWED PRIOR TO
 INSTALLATION. IT IS ACCEPTABLE TO PROVIDE PRODUCT
 APPROVALS AT THIS TIME, BUT A REVISION FEE WILL BE
 CHARGED IF THE PRODUCT IS CHANGED AFTER ISSUANCE.
  
  