2017-10-12 11:30:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-15 FLUSH CONTROLS SHALL COMPLY WITH FBC ACC
 604.6 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET.
  
 2. SHT.S-2 DN -23 AND THE PLUMBING SHEETS PLEASE
 CLARIFY WILL THE EXISTING STORM WATER SYSTEM REMAIN THE
 SAME PROVIDE NOTE ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. P-3 SANITARY ISOMETRIC DRAWING THE FLOOR DRAINS
 ARE NOT VENTED THEY SHALL COMPLY WITH FBC PL 901.2.1
  
 4. SHT. P-3 SANITARY ISOMETRIC DRAWING THE EYE WASH IS
 NOT VENTED IT SHALL COMPLY WITH FBC PL 901.2.1
  
 5. SHT. P-3 SANITARY ISOMETRIC DRAWING THE VENTS FOR
 THE LAVATORY AND WATER CLOSET IN THE HANDICAP STALL OF
 WOMENS BATHROOM SHALL EXTEND THROUGH 2ND FLOOR AND
 REVENT ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES ON THE
 2ND FLOOR. PER FBC PL 905.5
  
 6. SHT. P-3 SANITARY ISOMETRIC DRAWING THE SOIL STACK
 FROM 2ND FLOOR SHALL CONNECT TO THE BUILDING BRANCH
 DRAIN DOWN STREAM OF THE WATER CLOSET. PER FBC PL 912.1
  
 7.SHT. P-3 SANITARY ISOMETRIC DRAWING A CLEANOUT SHALL
 BE PROVIDED AT THE BASE OF EACH WASTE OR SOIL STACK.
 PER FBC PL 708.3.4
  
 8. PLEASE PROVIDE A DOMESTIC WATER ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 9. PLEASE SHOW COMPLIANCE WITH FBC PL 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 10. PLEASE SHOW COMPLIANCE WITH FBC PL 606.1 LOCATION
 OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE
 IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY
 RESIDENTIAL OCCUPANCIES.
  
 11. PLEASE SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR
 TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
 [E] 607.5 PIPE INSULATION.
 HOT WATER PIPING IN AUTOMATIC TEMPERATURE MAINTENANCE
 SYSTEMS SHALL BE INSULATED WITH 1 INCH (25 MM) OF
 INSULATION HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 BTU
 PER INCH/H ? FT2 ? ?F (1.53 W PER 25 MM/M2 ? K). THE
 FIRST 8 FEET (2438 MM) OF HOT WATER PIPING FROM A HOT
 WATER SOURCE THAT DOES NOT HAVE HEAT TRAPS SHALL BE
 INSULATED WITH 0.5 INCH (12.7 MM) OF MATERIAL HAVING A
 CONDUCTIVITY NOT EXCEEDING 0.27 BTU PER INCH/H ? FT2 ?
 ?F (1.53 W PER 25 MM/ M2 ? K).
  
 12. PLEASE SHOW COMPLIANCE WITH FBC PL 604.9 WATER
 HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 13. PLEASE SHOW COMPLIANCE WITH FBC PL 608.3 DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS.
 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS AND
 OTHER APPLIANCES AND DEVICES THAT HANDLE OR TREAT
 POTABLE WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
  
 14. PLEASE PROVIDE A RISER DIAGRAM FOR PROCESS PIPING
 AND STEAM PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  