Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop M
Sequence Number 1
Notes
Date Text
2017-10-16 17:56:391ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES.
 PERMIT #17090272
 10/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTIONS C101.4.4 AND C101.4.5 FBC-14
 ENERGY CONSERVATION: THE PROPOSED PROJECT IS DETERMINED
 TO BE A CHANGE OF OCCUPANCY AND ALSO A CHANGE IN SPACE
 CONDITIONING WHICH REQUIRES FULL COMPLIANCE WITH THE
 CURRENT ENERGY CODE. THE SUBMITTED FORM C402-2014 IS A
 COMPLIANCE FORM USED FOR ALTERATIONS AND CANNOT BE USED
 IN THIS CASE- SECTION C101.5.1.1. PLEASE
  
 SEE SECTION C401.2 AND SUBMIT AN ENERGY COMPLIANCE FORM
 UTILIZING ONE OF THE METHODS DESCRIBED THERE.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. CLARIFY IF VENTILATION
 FOR THE BOILER ROOM AND THE MOLASSES TANK ROOM IS TO BE
 PROVIDED, AND IN ACCORDANCE WITH WHICH CODE STANDARD
  
 OR BY MANUFACTURER'S SPECIFICATIONS.
  
 3) CORRECT KEYNOTE 1 ON SHEET M-1 WHICH IS INDICATING
 BATHROOM EXHAUST AT THE O/A INTAKE FOR THE RELOCATED 10
 TON AC SYSTEM. NOTE 1 IS ALSO INCORRECTLY SHOWN AT THE
 COMBUSTION AIR OPENING FOR THE BOILER ROOM- PLEASE
 CORRECT. REFER TO SECTION 401.4(2): THE LOCATION OF THE
 O/A INTAKE APPEARS TO BE WITHIN 10' OF THE STREET-
 PLEASE RELOCATE THE INLET.
  
 4) AC SYSTEMS: A) NON-COMBUSTIBLE DOORS ARE REQUIRED
 FOR THE SECOND FLOOR MECHANICAL ROOM AND THE STORAGE 2
 ROOM WHERE THE AIR HANDLERS ARE LOCATED- SEE SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION AND SECTION 602
 FBC-14 MECHANICAL. B) PROVIDE CONDENSATE DISPOSAL
 PLANS- SECTION 307. C) PROVIDE STRUCTURAL ENGINEERING
 FOR INSTALLATION OF THE CONDENSER PADS AND
  
 ANCHORING DETAILS FOR MOUNTING THE CONDENSERS TO THE
 PADS- SECTION 301.15. D) FLOOD HAZARD- SEE SECTION
 301.16: THE CONDENSERS SHALL BE INSTALLED AT OR ABOVE
 THE ELEVATION REQUIRED BY SECTION 1612 FBC-14 BUILDING.
 REFER ALSO TO BUILDING REVIEW COMMENTS REQUIRING A
 SURVEY AND ELEVATION CERTIFICATES.
  
 5) BOILER: A) PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED PER
 SECTION 304 FBC-14 FUEL GAS. B) PROVIDE A VENTING PLAN
 INDICATING THE TYPE AND SIZE OF FLUE PIPE, LENGTH OF
 THE VENT RUN, TERMINATION HEIGHT ABOVE THE ROOF, AND
 CLEARANCE DISTANCES TO GRAVITY AND MECHANICAL AIR
 INTAKES- SECTION 503 FBC-14 FUEL GAS. C) SUBMIT
 MANUFACTURER'S
  
 SPECIFICATIONS FOR THE BOILER AND ALL ASSOCIATED
 EQUIPMENT- SECTION 631.
  
 6) PROVIDE A MECHANICAL PLAN FOR THE DISTILLERY
 PROCESS: A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE CHILLER, AND ALL DISTILLERY TANKS AND EQUIPMENT
 LISTED IN THE KEYNOTES ON S4- PN-32, 33, 34, 35, 36,
 37, 38, 39, 40, & 41. B) PROVIDE A CHILLED WATER PIPING
 LAYOUT PLAN. C) PROVIDE TANK VENTING DETAILS. D)
 PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 CHILLER, AND VERIFY
  
 COMPLIANCE WITH FLOOD ELEVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  