Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop G
Sequence Number 1
Notes
Date Text
2017-10-12 11:52:161ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 BOILER AND ASSOCIATED EQUIPMENT, TANKLESS HEATERS AND
 FLUE PIPING. PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 3. THE PLUMBING PLAN SHOWS 2 TANKLESS WATER HEATERS THE
 GAS RISER ONLY SHOWS 1 TANKLESS WATER HEATER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. G-1 GAS RISER THE BRANCH PIPING FEEDING THE
 TANKLESS WATER HEATERS IS UNDERSIZED FOR 2 HEATERS AS
 SHOWN ON PLUMBING PLAN IT SHALL BE 2". PER FBC FG TABLE
 402.4(1)
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  