Plan Review Notes
Plan Review Notes For Permit 17090272
Permit Number 17090272
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-05 17:12:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS PROJECT APPEARS TO BE A "SUBSTANTIAL
 IMPROVEMENT" AS THE VALUE OF THE IMPROVEMENT EXCEEDS
 50% OF THE STRUCTURE VALUE PER PALM BEACH COUNTY
 PROPERTY APPRAISER ($310,000 PERMIT VALUE / $578,777
 PAPA STRUCTURE VALUE). AS THE BFE IS 13' NGVD29,
 LOCATED IN FLOOD ZONE A9, PER FIRM PANEL 120229 0020B,
 WITH A 1' FREEBOARD PER CITY OF WEST PALM BEACH
 MUNICIPAL CODE 94-546(B)(2).
  
 FBC EB 403.2, THE STRUCTURE AND EQUIPMENT ARE TO COMPLY
 WITH THE MINIMUM DFE OF 14' NGVD29. IT APPEARS THAT THE
 STRUCTURE LIKELY COMPLIES (ALTHOUGH ACTUAL FFE IS NOT
 CLEAR, SEE OTHER COMMENT REGARDING LOWEST AND NEXT
 FLOOR); COMPLIANCE FOR MECHANICAL EQUIPMENT NOT CLEAR.
  
 2. S1 DEPICTS TWO SEPARATE BUILDINGS CONNECTED WITH A
 COMMON WALL, BOTH LABELED AS "EXISTING ONE STORY
 BUILDING". THEY APPEAR TO BE ONE BUILDING, STRUCTURALLY
 CONNECTED. IF THEY ARE TWO BUILDINGS, REVISE PLAN TO
 STATE HOW THIS HAS BEEN DETERMINED. IF THEY ARE ONE
 BUILDING, REVISE THE LABELS.
  
 3. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107, FBC EB 403.2.
  
 4. FBC EB 403.2, FBC B 1603.1.7, SHEET S4 SHOWS
 ELEVATION AS 0'0", AND REFERS TO NAVD88 ELEVATIONS ON
 SURVEY. NO SURVEY WAS PROVIDED.
  
 PLEASE REVISE S4 TO INCORPORATE THE EXISTING AND
 PROPOSED FFE. CLARIFY FFE FOR THE CONNECTED BUILDING
 CURRENTLY LABELED AS "EXISTING ONE STORY BUILDING".
  
 IT IS RECOMMENDED THAT, SINCE THE APPLICATION WAS
 SUBMITTED PRIOR TO OCTOBER 5, 2017, THAT THE VERTICAL
 DATUM ON THE BUILDING PLANS UTILIZE NGVD29. IF NAVD88
 IS UTILIZED ON THE BUILDING PLANS, INCLUDE A CONVERSION
 (AND NOTE METHOD OF CONVERSION) SO COMPLIANCE WITH THE
 REQUIREMENTS OF FBC EB 403.2 IS CLEAR.
  
 ALL ELEVATION CERTIFICATES CERTIFIED OCTOBER 5, 2017
 AND LATER ARE TO UTILIZE NAV88 AND INCLUDE A CONVERSION
 TO NGVD29.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 5. FBC EB 403.2, REVISE THE PLAN TO CLARIFY THAT FFE
 AND ALL EQUIPMENT SERVICING THE BUILDING ARE PROPOSED
 TO BE ELEVATED OR INSTALLED AT > 14'NGVD29. REVISE THE
 PLAN TO INCLUDE ALL EQUIPMENT SERVICING THE BUILDING.
  
 6. FBC EB 403.2, COMMENTS REGARDING THE ELEVATION
 CERTIFICATE PROVIDED:
  
 A. PROVIDE A "CONSTRUCTION DRAWINGS" ELEVATION
 CERTIFICATE TO SHOW/CLARIFY PROPOSED CONSTRUCTION.
  
 B. ELEVATION CERTIFICATE ITEM C2(E), MECHANICAL
 EQUIPMENT ELEVATION IS BLANK; PLEASE REVISE WITH NOTES
 IF NEEDED. WATER HEATER? ROOFTOP MECHANICAL EQUIPMENT?
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 C. THE ELEVATION CERTIFICATE, ITEM C2A TOP OF BOTTOM
 FLOOR, 14.54, AND ITEM B, TOP OF NEXT FLOOR, AS 14.09.
 PLEASE CORRECT. FFE IS NOT CLEAR. NOTE THAT BOTH COMPLY
 WITH BFE + 1' FREEBOARD.
  
 D. A1, OWNER ON EC IS "HEALTHCARE REAL ESTATE CAPITAL";
 THIS IS IN CONFLICT WITH PROPERTY APPRAISER RECORDS.
 REVISE OR CLARIFY.
  
 E. A9 INDICATES AN 1813 SF GARAGE, C2(D) ELEVATION IS
 "NA" AND SHEET S1 DOES NOT SHOW A GARAGE, PLEASE
 CORRELATE.
  
 F. C2 BENCHMARK, SEE INSTRUCTIONS: INCLUDE PERMANENT
 IDENTIFIER (PID). ON THE EC, BENCHMARK UTILIZED IS
 "LOCAL"; IT IS NOT CLEAR IF THAT MEANS A LOCAL
 BENCHMARK, OR IF THE NAME OF THE BENCHMARK IS "LOCAL".
  
 G. SECTION E (E1-E5), PLEASE REVISE TO INCLUDE "NA" FOR
 FIELDS WHICH ARE CURRENTLY.
  
 7. THIS PERMIT WILL BE ISSUED WITH PROVISO; PRIOR TO
 CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 ELEVATION CERTIFICATE OR FORM BOARD SURVEY WITH
 ELEVATIONS WILL BE REQUIRED. PRIOR TO FINAL INSPECTION,
 A "FINISHED CONSTRUCTION" ORIGINAL SIGNED AND SEALED
 ELEVATION CERTIFICATE, WITH COLOR PHOTOGRAPHS OF ALL
 SIDES OF THE STRUCTURE AND EXTERIOR MECHANICAL
 EQUIPMENT (WITH TIE DOWNS VISIBLE IN PHOTOS) WILL BE
 REQUIRED. SUBMIT THE "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE AT THE BUILDING DIVISION AS A SUBMITTAL (NO
 FEE) FOR REVIEW WHEN AVAILABLE.
  
 8. FBC EB 301.1, THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY (CH 10). A CURSORY LOOK INTO RECORDS FOR THIS
 BUILDING APPEAR TO REFLECT THAT CURRENT OCCUPANCY IS
 BUSINESS OR STORAGE. IF THIS IS A CHANGE OF OCCUPANCY,
 REVISE PLAN TO NOTE THE CHANGE OF OCCUPANCY FROM
 CURRENT OCCUPANCY TO MIXED OCCUPANCY F1, M, AND
 POSSIBLE ANOTHER OCCUPANCY (TASTING/TOURS).
  
 VIA A RECORDS RESEARCH REQUEST, PLEASE DETERMINE THE
 CURRENT OCCUPANCY AS PERMITTED; CONTACT
 [email protected].
  
 9. THE PROCESSING PORTION HAS TEXT WHICH STATES:
 "TASTING/TOURS". SEE FBC B 302: "A ROOM OR SPACE THAT
 IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED."
  
 NOT ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE. IF
 THIS AREA WILL BE USED FOR TOURS/TASTING, IT APPEARS
 THAT THE AREA WOULD ALSO BE SUBJECT TO ACCESSIBILITY.
 AN F1 OCCUPANT LOAD OF 51 IS DECLARED; IS THE
 TOURS/TASTING OCCUPANT LOAD IN ADDITION TO THIS
 OCCUPANT LOAD OR INCLUSIVE? WHAT IS THE OCCUPANT LOAD
 ANTICIPATED FOR THE TOURS/TASTING VS. F1 OCCUPANT LOAD?
  
 10. IF THIS IS A CHANGE OF OCCUPANCY, SEE FBC EB TABLES
 1012.4 THROUGH 1012.6. IN ANY CASE WHERE CHANGE OF
 OCCUPANCY IS MADE TO A HIGHER HAZARD, REVISE PLAN TO
 SHOW COMPLIANCE.
  
 11. SEE IMPACT FEE REVIEW. PLAN IS TO BE CLEAR AS TO
 PREVIOUS USE/OCCUPANCY (PERMITTED AND INSPECTED) SO
 THEY CAN PERFORM AN ACCURATE REVIEW.
  
 IT APPEARS THAT ADDITIONAL SQUARE FOOT AREA IS BEING
 ADDED (CREATING A 2ND FLOOR). REVISE THE PLAN TO
 CLARIFY EXISTING SF AREA, PROPOSED NEW.
  
 12. THE DOOR TO "MOLASSES TANKS" ROOM LACKS THE
 MANEUVERING CLEARANCE REQUIRED BY FBC A TABLE 404.2.4.1
 (A), 18" PULL SIDE. THIS APPEARS TO BE A WORK AREA; SEE
 FBC A 206.2.8 REGARDING EMPLOYEE WORK AREAS. IF AN
 EXEPTION IS APPLICABLE, REVISE PLAN TO INCLUDE
 EXCEPTION.
  
 13. FBC A TABLE 404.2.4.1(A), REVISE PLAN TO SHOW 18"
 MANEUVERING CLEARANCE REQUIRED FOR DOOR DR 3.
  
 14. S4, A DASHED LINE (3') AT THE ENTRY DOOR IS SHOWN.
 CLARIFY WHAT THIS IS. REVISE PLAN TO SHOW ACCESSIBLE
 ROUTE AT ENTRY DOOR WHICH COMPLIES WITH FBC A 303.2
 (SEE ALSO FBC A 202.3).
  
 15. PN25 MERCANTILE AREA, S4, ACCESSIBLE COUNTER SHOWN
 30" DEPTH. PROVIDE A DETAIL OR REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 PN25 TASTING TOURS AREA, PROVIDE A DETAIL TO SHOW
 COMPLIANCE WITH FBC A 902.3.
  
 16. PN25, PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC
 A 227 (CHECK OUT AISLE).
  
 17. NO FIRE SPRINKLER INFORMATION PROVIDED. EITHER
 PROVIDE A PLAN OR INCORPORATE ALL REQUIREMENTS OF FBC B
 404.6 EXCEPTION INTO THE PLAN.
  
 18. REVISE PLAN TO INDICATE FLOOR DESIGN LIVE LOAD, OR
 ADVISE WHERE THIS INFORMATION CAN BE LOCATED. REVISE
 PLAN TO INCLUDE THE REQUIREMENTS OF FBC B 106.1, 106.2:
  
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A COMMERCIAL OR
 INDUSTRIAL BUILDING IS OR HAS BEEN DESIGNED TO EXCEED
 50 PSF (2.40 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE
 CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF EACH
 STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT
 SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL
 NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY
 SECTION 106.1, HAVE BEEN INSTALLED.
  
 19. LS2, TRAVEL DISTANCE IS SHOWN AS 94' TO THE BASE OF
 THE STAIR. SEE FBC B 1016.3, EXIT ACCESS TRAVEL
 DISTANCE IS TO BE MEASURED FROM THE MOST REMOTE POINT
 WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH
 OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT. IT APPEARS THAT THE MEASUREMENT IS
 TO THE BASE OF THE STAIR, AT WHICH POINT OCCUPANT IS
 REQUIRED TO GO THROUGH THE FIRST FLOOR TO REACH AN
 EXIT, PLEASE REVISE OR CLARIFY. SEE ALSO FBC B 404.9
 (<200' TRAVEL DISTANCE).
  
 20. FBC 107, PALLET RACKS, REVISE PLAN TO INCLUDE
 HEIGHT LIMITATION.
  
 21. FBC A 213.1, 206.2.3, DEFINITION OF "ADDITION"
 106.5, 202.2, PRIOR TO RESUBMITTING, SEND VIA EMAIL THE
 RATIONALE FOR NOT PROVIDING ACCESSIBLE BATHING
 FACILITIES ON THE FIRST FLOOR. ALSO PROVIDE RATIONALE
 FOR LACK OF ACCESSIBLE BATHING FACILITY ON THE 2ND
 FLOOR.
  
 SEE ALSO HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-ST
 ANDARDS/BUILDINGS-AND-SITES/ABOUT-THE-ADA-STANDARDS/GUI
 DE-TO-THE-ADA-STANDARDS/CHAPTER-4-ACCESSIBLE-ROUTES
  
 22. REVISE PLAN TO EXPLAIN PURPOSE OF INTERIOR WINDOWS
 ON 2ND FLOOR, FBC 107. IS THIS FOR VISITORS, EMPLOYEES,
 AND WHY? PLEASE SEND VIA EMAIL PRIOR TO RESUBMITTAL SO
 IT CAN BE DETERMINED IF ADDITIONAL INFORMATION IS
 REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
 ANY OF THE ISSUES/INQUIRIES RAISED IN THIS PLAN REVIEW.
  