| 2017-10-07 10:33:02 | BRISTOL UNIT REVISIONS: |
| | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17090230 |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. SUITE: UNIT 16A |
| | CONT: SUFFOLK |
| | TEL: 561-827-3678 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | SUBJECT TO FAIR HOUSING! |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 07/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 126.41-A2.90-16A. UNIT 16A. |
| | |
| | 1A) THE STUDY HAS A PAIR OF POCKET DOORS IDENTIFIED AS |
| | (U02K). PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE |
| | INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1B) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS |
| | DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1C) HER MASTER CLOSET HAS A SINGLE POCKET DOOR |
| | IDENTIFIED AS (U05V). POCKET DOORS SHOWN IN THE OPEN |
| | POSITION MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR |
| | WIDTH OF 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR |
| | HOUSING SECTION 100.205.(C)(2)(2). |
| | 1D) HER MASTER CLOSET HAS A SINGLE POCKET DOOR |
| | IDENTIFIED AS (U05V). PLEASE PROVIDE WHAT TYPE OF |
| | HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE |
| | FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE |
| | THAT HAVE LIMITED HAND MOBILITY. 2014 FBC- |
| | ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2). |
| | FIGURE 1( C ). |
| | |
| | 1E) BEDROOM # 2 & 3 THE CLOSET POCKET DOOR IS TO COMPLY |
| | WITH: |
| | 1E)(1) POCKET DOORS SHOWN IN THE OPEN POSITION MEASURE |
| | 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 |
| | INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2). |
| | 1E)(2) PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE |
| | INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1F) BEDROOM # 4 SHOWS CLOSET BY-PASS DOORS, PLEASE SHOW |
| | COMPLIANCE WITH: |
| | 1F)(1) POCKET DOORS SHOWN IN THE OPEN POSITION MEASURE |
| | 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 |
| | INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2). |
| | |
| | 1F)(2) PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE |
| | INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 2A) SHEET 242.41-A6-66 FINISHES UNIT 16A: |
| | THE POWDER ROOM FLOOR INDICATES WOOD OAK FLOORING. |
| | PLEASE NOTE WE HAVE NOT SEEN HOW THE MARBLE AND WOOD |
| | FINISH FLOOR DETAILS. IN PAST MEETINGS WITH THE DESIGN |
| | TEAM AND SUFFOLK REPRESENTATIVES THERE WAS TALK OF |
| | VARIOUS WOOD SUB-FLOOR SYSTEMS FOR WOOD FLOORS. |
| | |
| | 2010 FBC-B 805.1.1 SUBFLOOR CONSTRUCTION. FLOOR |
| | SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE |
| | CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE |
| | BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND |
| | THE FLOORING IS EITHER SOLIDLY FILLED WITH |
| | NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE |
| | WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES |
| | SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS |
| | OR WALLS. |
| | OR |
| | 2010 FBC-B 805.1.2 WOOD FINISHES FLOORING. WOOD FINISH |
| | FLOORING IS PERMITTED TO BE ATTACHED DIRECTLY TO THE |
| | EMBEDDED OR FIREBLOCKED WOOD SLEEPERS AND SHALL BE |
| | PERMITTED WHERE CEMENTED DIRECTLY TO THE TOP SURFACE OF |
| | FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES OR DIRECTLY TO A |
| | WOOD SUBFLOOR ATTACHED TO SLEEPERS AS PROVIDED FOR IN |
| | SECTION 805.1.1. |
| | |
| | 2B) FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR |
| | INSULATION (FBC-B 2010) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR |
| | PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF |
| | THERE IS A DROP CEILING WITH OR WITHOUT INSULATION OR |
| | PROVIDE ONSITE TESTING TO THE LISTED BELOW ASTM |
| | STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2B)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2B)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |