Plan Review Notes
Plan Review Notes For Permit 17090219
Permit Number 17090219
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-09-15 13:05:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.1 - THERE IS NO INDICATION OF REVIEW OR
 DESIGN WITH ANY FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 INDICATING NOTE.
  
  
  
 2) SHEET A 0.1 - THERE IS NO REFERNCE TO THE EXISTING
 OCCUPANCY TYPE AND IF THERE IS AN EXISTING FIRE
 SPRINKLER OR FIRE ALARM SYSTEM.
  
 PLEASE INDICATE THE OCCUPANCY TYPE AND ANY EXISTING
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM.
  
  
  
 3) SHEET A 1.0 - THE PROPOSED PROJECT REMOVES WALLS AND
 INSTALLS NEW WALLS THAT MAY AFFECT THE THE EXISTING
 FIRE SPRINKLER COVERAGE AND FIRE ALARM SYSTEM DEVICES
 AND FUNCTION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE THE APPLICABLE NOTE.
  
  
  
 4) SHEET A 1.1 - NOTE 23 INDICATES ELECTRICAL WORK,
 WIRING AND EQUIPEMNT; HOWEVER, THERE IS NO ELECTRICAL
 DRAWING SHEET.
  
 PLEASE PROVIDE AN ELECTRICAL DRAWING SHEET SHOWING THE
 ELECTRIC SERVICE PANEL INFORMATION AND ALL APPLICABLE
 WIRING ROUTES AND EQUIPMENT LOCATIONS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  