| 2017-09-15 13:05:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.1 - THERE IS NO INDICATION OF REVIEW OR |
| | DESIGN WITH ANY FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A |
| | INDICATING NOTE. |
| | |
| | |
| | |
| | 2) SHEET A 0.1 - THERE IS NO REFERNCE TO THE EXISTING |
| | OCCUPANCY TYPE AND IF THERE IS AN EXISTING FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM. |
| | |
| | PLEASE INDICATE THE OCCUPANCY TYPE AND ANY EXISTING |
| | FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM. |
| | |
| | |
| | |
| | 3) SHEET A 1.0 - THE PROPOSED PROJECT REMOVES WALLS AND |
| | INSTALLS NEW WALLS THAT MAY AFFECT THE THE EXISTING |
| | FIRE SPRINKLER COVERAGE AND FIRE ALARM SYSTEM DEVICES |
| | AND FUNCTION. |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE |
| | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE THE APPLICABLE NOTE. |
| | |
| | |
| | |
| | 4) SHEET A 1.1 - NOTE 23 INDICATES ELECTRICAL WORK, |
| | WIRING AND EQUIPEMNT; HOWEVER, THERE IS NO ELECTRICAL |
| | DRAWING SHEET. |
| | |
| | PLEASE PROVIDE AN ELECTRICAL DRAWING SHEET SHOWING THE |
| | ELECTRIC SERVICE PANEL INFORMATION AND ALL APPLICABLE |
| | WIRING ROUTES AND EQUIPMENT LOCATIONS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |