| 2017-09-27 07:55:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. SHEET A0.1, FBC EB 504, THIS IS A LEVEL TWO |
| | ALTERATION (NOT LEVEL ONE), REVISE PLAN. |
| | |
| | 2. IT IS NOT CLEAR IF FBC ACCESSIBILITY APPLIES, SEE |
| | FBC A 106. A CHURCH WHICH IS NOT A PLACE OF PUBLIC |
| | ACCOMMODATION IS EXEMPT. HOWEVER, IF THE PREMISES ARE |
| | RENTED OUT FOR FUNCTIONS (WEDDINGS, CONFERENCES, ETC.), |
| | IT IS POSSIBLE THAT THE FACILITY IS CONSIDERED A PLACE |
| | OF PUBLIC ACCOMMODATION AND SUBJECT TO THE REQUIREMENTS |
| | OF FBC ACCESSIBILITY. |
| | |
| | IF EXEMPT, PROVIDE INFORMATION REGARDING EXEMPTION. IT |
| | IS SUGGESTED THAT YOU SEND THE PROPOSED LANGUAGE TO ME |
| | VIA EMAIL PRIOR TO RESUBMITTAL. THE JUSTIFICATION FOR |
| | EXEMPTION MAY BE MADE EITHER BY DESIGN PROFESSIONAL ON |
| | THE PLAN OR IN THE FORM OF A LETTER FROM THE CHURCH ON |
| | LETTERHEAD. CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 3. PURPOSE OF THE "WORK ALCOVE" IS NOT CLEAR (SHEET |
| | A1.0 "NEW WORK NOTES"). "WORK AREAS" ARE GENERALLY |
| | EXEMPT, BUT THE NATURE OF THE "WORK AREAS" IS NOT |
| | CLEAR, REVISE PLAN TO CLARIFY. |
| | |
| | 4. VALUE APPEARS LOW, FBC 109. IF SUBJECT TO |
| | ACCESSIBILITY, ACCESSIBLE ROUTE TO THE ALTERED AREA |
| | (PULPIT) MAY BE REQUIRED, FBC A 202.3. A COST BREAKDOWN |
| | MAY BE REQUIRED IN THE EVENT OF DISPROPORTIONATE COST. |
| | NOT ENOUGH INFORMATION ON THE PLAN TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 5. PLAN REFERS TO "REMOVED WINDOWS"; SHOULDN'T THIS BE |
| | "PROPOSED" WORK? FBC 107. |
| | |
| | 6. FBC 107, FBC B CHAPTER 3, REVISE PLAN TO INCLUDE |
| | OCCUPANCY CLASSIFICATION. |
| | |
| | |
| | |
| | |