Plan Review Notes
Plan Review Notes For Permit 17090214
Permit Number 17090214
Review Stop G
Sequence Number 2
Notes
Date Text
2017-11-30 06:47:521) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATERS. THE LOCATION OF
 THE TANKLESS WATER HEATERS SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL.2014 FBCR SEC.
 G2406.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 REGULATORS.2014 FBCR SEC. G2421.1.
 3) SHT. A-7 REFERS TO A SECTION "B" ON THE GAS DRAWING.
 THERE IS NO "B" SECTION ON THE GAS DRAWING. CLARIFY.
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL
 GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4,
 G2412.8, G2413.1, G2413.2, & G2413.3.
 5) SHOW THE DISTANCE OF THE POOL HEATER FROM THE
 PRESSURE REGULATOR. THE MINIMUM SIZE MAY NEED TO BE
 INCREASED TO 1" GALVANIZED PIPE.
 6) THE LOCATION OF THE POOL HEATER ON THE GAS RISER
 DOES NOT CORRELATE WITH THE FLOOR PLAN.
 7) THE GAS RISER APPEARS TO SHOW PE PIPE UNDER THE
 BUILDING SLAB. PE PIPE SHALL ONLY BE INSTALLED OUTDOORS
 UNDERGROUND ONLY. 2014 FBCR SEC. G2415.17.1.
 8) MAKEUP AIR SHALL BE PROVIIDED IN THE LAUNDRY ROOM
 FOR THE GAS DRYER IN ACCCORDANCE WITH FBCR SEC.G2439.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
2017-11-30 06:18:421)