| 2017-11-30 06:47:52 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION |
| | MANUAL FOR THE TANKLESS WATER HEATERS. THE LOCATION OF |
| | THE TANKLESS WATER HEATERS SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION MANUAL.2014 FBCR SEC. |
| | G2406.1. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS |
| | REGULATORS.2014 FBCR SEC. G2421.1. |
| | 3) SHT. A-7 REFERS TO A SECTION "B" ON THE GAS DRAWING. |
| | THERE IS NO "B" SECTION ON THE GAS DRAWING. CLARIFY. |
| | 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. |
| | 5) SHOW THE DISTANCE OF THE POOL HEATER FROM THE |
| | PRESSURE REGULATOR. THE MINIMUM SIZE MAY NEED TO BE |
| | INCREASED TO 1" GALVANIZED PIPE. |
| | 6) THE LOCATION OF THE POOL HEATER ON THE GAS RISER |
| | DOES NOT CORRELATE WITH THE FLOOR PLAN. |
| | 7) THE GAS RISER APPEARS TO SHOW PE PIPE UNDER THE |
| | BUILDING SLAB. PE PIPE SHALL ONLY BE INSTALLED OUTDOORS |
| | UNDERGROUND ONLY. 2014 FBCR SEC. G2415.17.1. |
| | 8) MAKEUP AIR SHALL BE PROVIIDED IN THE LAUNDRY ROOM |
| | FOR THE GAS DRYER IN ACCCORDANCE WITH FBCR SEC.G2439.4. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |