| Date |
Text |
| 2017-10-03 17:41:37 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17090214 |
| | 10/3/2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY FORM R405 IS SPECIFYING A "WORST CASE" |
| | COMPLIANCE HOWEVER THE PROPSED SINGLE FAMILY RESIDENCE |
| | IS NOT A MODEL HOME. PLEASE SEE SECTION R405.4.2 FBC-14 |
| | ENERGY CONSERVATION AND PROVIDE THE STREET ADDRESS OF |
| | THE RESIDENCE ON THE FORM AND REPLY "NO" TO WORST CASE. |
| | |
| | 2) PLEASE CORRECT THE AC SYSTEM CALCULATIONS WHICH ARE |
| | ALSO SPECIFYING A WORST CASE AND SUBMIT CALCULATIONS |
| | ACCORDING TO THE ACTUAL DIRECTIONAL ORIENTATION OF THE |
| | NEW HOUSE- SECTION R403.6.1. |
| | |
| | 3) PLEASE CLEARLY LABEL AHU-1 & 2 IN GARAGE-1 AND |
| | INDICATE IF THEY ARE IN THE GARAGE OR ATTIC SPACE. |
| | PLEASE NOTE AN ACCESS PANEL WILL BE REQUIRED FOR ATTIC |
| | INSTALLATIONS. VERIFY COMPLIANCE WITH SECTION R403.2.4 |
| | WITH NOTES ON THE PLAN: |
| | |
| | R403.2.4 AIR-HANDLING UNITS. |
| | AIR HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| | WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| | R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| | COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | |
| | 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| | |
| | 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| | PROPERLY. |
| | |
| | 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. |
| | |
| | 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | |
| | NOTICE TO HOMEOWNER |
| | |
| | A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR |
| | HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, |
| | EFFICIENT, AND ECONOMIC OPERATION OF THE |
| | AIR-CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR |
| | MAINTENANCE IS PERFORMED. YOUR AIR-CONDITIONING SYSTEM |
| | IS EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: (1) A |
| | DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN |
| | IS NOT WORKING PROPERLY OR (2) A DEVICE THAT WILL SHUT |
| | THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT |
| | WORKING. TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO |
| | AVOID DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU |
| | ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE |
| | EACH SEASON OF PEAK OPERATION. |
| | |
| | 4) SUBMIT GAS PLANS INCLUDING: A) COMBUSTION AIR |
| | CALCULATION FOR EACH APPLIANCE- SECTION G2407.1. B) GAS |
| | PIPING LAYOUT AND ISOMETRIC DRAWING- SECTIONS G2413 & |
| | 2414. C) GAS VENTING PLANS FOR EACH APPLIANCE- G2427 . |
| | D) PRODUCT DATA SHEETS FOR ALL GAS-FIRED APPPLIANCES |
| | INCLUDING THE RANGE, DRYER, WATER HEATER AND ANY OTHER |
| | UNITS NOT SHOWN ON THE DRAWINGS. |
| | |
| | 5) SUBMIT A PRODUCT DATA SHEET FOR THE RANGE HOOD. IT |
| | APPEARS THAT MAKEUP AIR IS BRING PROVIDED FOR THE |
| | EXHAUST SYSTEM. CLARIFY HOW THE O/A DAMPER AND EXHAUST |
| | HOOD ARE FUNCTIONING TOGETHER |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |