| 2017-10-04 14:25:06 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. |
| | 402.2 |
| | |
| | 2. PLEASE SHOW REGULATORS AND DRIP LEGS ON RISER. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. A-1 SHOWS POOL HEATER ON THE SAME SIDE OF THE |
| | HOUSE AS THE COOK TOP THE RISER SHOWS IT ON THE |
| | OPPOSITE SIDE OF THE HOUSE PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. THE NOTE ON SHT A-7 STATES .5 PSI WITH DEVELOPED |
| | LENGTH OF 77FT PLEASE INDICATE ON THE RISER THE |
| | SECTIONS THAT ARE .5 PSI AND THE SECTIONS THAT ARE 2 |
| | PSI. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHOW THE LENGTH OF GALV PIPE BETWEEN THE TANKLESS |
| | HEATER AND THE COOK TOP AND THE CSST . FBC-2014 FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. |
| | |
| | 6. PLEASE EXPAND THE GAS RISER IT IS UNCLEAR HOW PIPING |
| | IS RUN AT THE POINT OF CONNECTION BETWEEN THE TANKLESS |
| | HEATER AND COOK TOP. FBC-2014 FUEL GAS, SECS. 402.4.1, |
| | 402.4.2. |
| | |
| | 7. PLEASE PROVIDE THE SIZING TABLES USED FROM THE FBC |
| | FG CH 4 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |