Plan Review Notes
Plan Review Notes For Permit 17090214
Permit Number 17090214
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-03 15:55:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A 2/0 COPPER FEEDING EACH OF THE
 200 AMP PANELS. THIS WIRE MUST BE SIZED PER
 310.15(B)(16) AS IT DOES NOT CARRY 100% OF THE LOAD.
 PROVIDE CORRECTION. NEC 310.15(B)(7), 310.15(B)(16);
 FBC RE 3602.2
 2. PROVIDE GFCI PROTECTION FOR POOL PUMP, SPA PUMP, SPA
 BLOWER. NEC 680.22(C), 680.44; FBC RE 4203.1.3, 4208.1
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. I DO NOT SEE THE CENTRAL VACUUM SYSTEM INCLUDED.
 LOAD CALCULATION MUST BE A TOTAL OF ALL ITEMS BEFORE
 DEMAND FACTORS ARE APPLIED. APPLYING DEMAND FACTORS TO
 EACH PANEL AND THEN ADDING THESE TOGETHER IS NOT
 ACCEPTABLE. NEC 220; FBC RE3602.3
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 6. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE,
 INCLUDING THE OUTLETS FOR GARAGE DOOR OPENER. NEC
 210.8; FBC RE3902.2
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 POOL, ETC. FBC 105.1, 107.2.1
 8. PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE
 FOR THE DESIGN. PROVIDE CORRECTION. FS 481.229; FBC
 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  