| Plan Review Notes For Permit 17090205 |
| Permit Number |
17090205 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-06-03 15:30:54 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090205 | | | 6/3/2019 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1. | | | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|