| 2019-06-06 09:26:35 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 17090205 |
| | REVIEWED: JUNE 5, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 105.1 FBC[AMENDED] PLEASE PROVIDE A REVISED PERMIT |
| | APPLICATION TO UPDATE THE DESCRIPTION AND VALUE OF |
| | PROJECT. |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN |
| | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW |
| | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE |
| | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR |
| | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS |
| | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION |
| | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, |
| | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR |
| | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL |
| | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED |
| | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS |
| | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE |
| | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN |
| | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW |
| | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED |
| | DEVELOPMENTS. |
| | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. |
| | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES |
| | COORDINATOR 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 107.5.3 FBC[AMENDED] SHEET LS-1 STATES TYPE V-B. THE |
| | CODE SUMMARY ON SAME SHEET SAYS TYPE II UNPROTECTED. |
| | - PLEASE CHANGE OR ERASE SINCE I BELIEVE V-B IS THE |
| | CONSTRUCTION TYPE. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, WINDOW MULL AND DOORS. |
| | - PLEASE PROVIDE DOOR AND WINDOW SCHEDULE TO SHOW SIZES |
| | AND DOOR TYPES (INCLUDE GLASS WALL SYSTEM). I RECEIVED |
| | PRODUCT APPROVAL (P.A.) FOR STOREFRONT. PLEASE CLARIFY |
| | WHERE THE STOREFRONT IS GOING. |
| | |
| | 3A) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. |
| | - I DIDN'T SEE P.A . FOR WINDOWS. ALSO, MULL IF NEEDED |
| | AT FRONT WINDOW. |
| | |
| | 3B) 4107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. |
| | - PLEASE PROVIDE 2 COPIES OF ANY NEW P.A.'S. WE WILL |
| | MAKE ADDITIONAL COPY OF ANY THAT ARE ALREADY SUBMITTED |
| | THAT GET APPROVED. |
| | |
| | 4) 502.1 FBC[CE] GENERAL. ADDITIONS TO AN EXISTING |
| | BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE |
| | PROVISIONS RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING |
| | THE UNALTERED PORTION OF THE EXISTING BUILDING OR |
| | BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS |
| | SHALL NOT CREATE AN UNSAFE OR HAZARDOUS CONDITION OR |
| | OVERLOAD EXISTING BUILDING SYSTEMS. AN ADDITION SHALL |
| | BE DEEMED TO COMPLY WITH THIS CODE IF THE ADDITION |
| | ALONE COMPLIES OR IF THE EXISTING BUILDING AND ADDITION |
| | COMPLY WITH THIS CODE AS A SINGLE BUILDING. ADDITIONS |
| | SHALL COMPLY WITH SECTION C502.2. ADDITIONS COMPLYING |
| | WITH ANSI/ASHRAE/IESNA 90.1. NEED NOT COMPLY WITH |
| | SECTIONS C402, C403, C404 AND C405. |
| | - PLEASE PROVIDE UPDATED ENERGY CALCULATIONS TO INCLUDE |
| | THE ADDITION. ALSO, USE THE CODE VERSION TO MATCH A AND |
| | S SHEETS. |
| | |
| | 5) 107.3.4.1 FBC[AMENDED] PRODUCT APPROVALS FOR ROOFING |
| | INSULATION ATTACHMENT. R VALUES SHOULD BE PROVIDED IN |
| | ENERGY CALCULATIONS. |
| | - PROVIDE ENHANCED ATTACHMENT FOR INSULATION PER |
| | LIMITATION 5.9 MECHANICALLY ATTACHED INSULATION. |
| | - ROOFING CAN BE DEFRRED SUBMITTAL IF REQUESTED. |
| | |
| | PROVISOS: |
| | |
| | AWNINGS TO BE DONE UNDER SEPARATE PERMIT. |
| | |
| | 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |