Plan Review Notes
Plan Review Notes For Permit 17090205
Permit Number 17090205
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-02 09:52:231ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR THE
 TOILET,LAVATORY, WA6TER FOUNTAIN ANDBREAKROOM SINK. PER
 FBC ACC 604.3.1/602.2 /606.2
  
 2. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE
 HEIGHT OF THE LAVATORY AND BREAKROOM SINK. PER FBC ACC
 606.3
  
 3. PLEASE SHOW COMPLIANCE WITH ACCESSIBILITY FOR THE
 HEIGHT OF THE MIRROR . PER FBC ACC 603.3
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES
  
 7. PROVIDE THE SQ-FT DRAINED BY SCUPPER AND DOWN SPOUTS
 INCLUDING PARAPET WALLS. PER FBC PL 1106.4 VERTICAL
 WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
  
 8. PLEASE PROVIDE COMPLIANCE WITH FBC PL 1108.1
 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
 WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY
 OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED
 WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE
 ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF
 THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON.
  
 9. THE LAVATORY FAUCETS SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  