2017-09-25 15:40:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090205
 9/25/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON AHU-1 SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 2) M-1: THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND SECTION 602 FBC-14 MECHANICAL.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA ON THE
 PLANS FOR INSTALLATION OF THE CONDENSERS, AND SUBMIT A
 CURRENT MIAMI-DADE NOA FOR THE ROOF STAND- NOA
 #14-1224.10 SPECIFIED ON THE PLAN HAS EXPIRED. THE
 ENGINEER OF RECORD MUST PROVIDE AN APPROVAL STAMP ON
 THE NEW NOA AND MARK OR HIGHLIGHT ALL APPLICABLE NOTES
 AND INSTALLATION DETAILS- SECTION 301.15 AND RULE 9N-3
 FAC.
  