| 2017-09-15 13:22:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) SHEET A 5 - THE DOOR SCHEDULE DOES NOT INDICATE |
| | HARDWARE OR LOCKS ON ANY DOOR. |
| | |
| | LOCKS AND HARDWARE ON EXIT DOORS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS |
| | AND CHAPTER 38, NEW BUSINESS OCCUPANCIES. |
| | |
| | 38.2.2 MEANS OF EGRESS COMPONENTS. |
| | 38.2.2.1 COMPONENTS PERMITTED. MEANS OF EGRESS |
| | COMPONENTS SHALL BE LIMITED TO THE TYPES DESCRIBED IN |
| | 38.2.2.2 THROUGH |
| | 38.2.2.12. |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| | TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, |
| | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND |
| | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE |
| | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS |
| | OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE ENSURE THE REQUIREMENTS ARE MET. A FIRE |
| | INSPECTOR SHALL VERIFY ON FIRE INSPECTION. |
| | |
| | |
| | |
| | 2) SHEET SP 1 - CONSTRUCTION AND DEMOLITION SHALL |
| | COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING |
| | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, |
| | 2013 EDITION. |
| | |
| | NOTE # 7 WAS ADDED TO THE SHEET. |
| | |
| | |