| Notes |
| Date |
Text |
| 2017-09-22 08:38:31 | THIS PLAN HAS BEEN APPROVED PROVISIONALLY: | | | | | | FOR ROUGH INSPECTION- PROVIDE LEGEND FOR HEXEGON | | | SHAPED, LETTERED NOTES ON PLAN. | | | | | | FOR FINAL INPSECTION- PROVIDE ACCURATE LOAD CALCULATION | | | FOR PANEL "M". | | | | | | PROVIDE AS-BUILT DRAWING SHOWING LOCATIONS OF PANELS "M | | | AND L". PANELS CANNOT BE LOCATED IN BATHROOMS OR | | | CLOSETS NEC 240.24 D&E | | | | | | CONFERENCE ROOM ALSO NEEDS 50% RECEPTACLE CONTROL | | | FBC-CE C.401.2 | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | DEVELOPMENT SERVICES DEPT. | | | CELL 561-657-1653 | | | [email protected] |
|