Plan Review Notes
Plan Review Notes For Permit 17090205
Permit Number 17090205
Review Stop E
Sequence Number 1
Notes
Date Text
2017-09-22 08:38:31THIS PLAN HAS BEEN APPROVED PROVISIONALLY:
  
 FOR ROUGH INSPECTION- PROVIDE LEGEND FOR HEXEGON
 SHAPED, LETTERED NOTES ON PLAN.
  
 FOR FINAL INPSECTION- PROVIDE ACCURATE LOAD CALCULATION
 FOR PANEL "M".
  
 PROVIDE AS-BUILT DRAWING SHOWING LOCATIONS OF PANELS "M
 AND L". PANELS CANNOT BE LOCATED IN BATHROOMS OR
 CLOSETS NEC 240.24 D&E
  
 CONFERENCE ROOM ALSO NEEDS 50% RECEPTACLE CONTROL
 FBC-CE C.401.2
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  