2018-01-10 14:35:282014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090202
 ADD: 1422 OKEECHOBEE RD.
 CONT: CEDARS ELECTRO-MECHANICAL, INC.
 TEL: 561-588-4088 IBRAHIM CHALHOUB
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 10/2018
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. THE SUBMITTED REPORT HAS PHOTO-COPIED
 SIGNATURES, SIGNATURES ARE PIXILATED.
 61G15-23.002(2)(B) FL. ADMIN. CODE.
  
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. PLEASE PROVIDE A
 SOILS REPORT FOR THE LOAD BEARING CAPACITY OF THE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) THE COVERSHEET:
 3A) COMPLIED.
  
 3B) SEMI-COMPLIED COMMENT C3 NEEDS TO BE COMPLIED WITH
 FIRST. THE PLANS INDICATE THIS BUILDING IS A S2
 OCCUPANCY. THE COVERSHEET LIST THE S2 OCCUPANCY OF 9906
 SQ. FT. AND THE BUSINESS OCCUPANCY 1400 SQ. FT. A TOTAL
 OF 11,306 SQ. FT. THE BUSINESS OCCUPANCY BEING 1400 SQ.
 FT. IS 0.12 % OR OVER 10% BUILDING AREA MAKING THE
 BUILDING A MIXED USE BUILDING, SEE FBC-B 508.2.1.
  
 3C) 2ND REQUEST. THE PLANS INDICATE THE OCCUPANCY
 SEPARATION WALL (FIRE BARRIER WALL) TO COMPLY WITH NFPA
 88A FIRE PARTITION.
 SEE 2014 FBC-B 707.3.9 SEPARATED OCCUPANCIES. WHERE THE
 PROVISIONS OF SECTION 508.4 ARE APPLICABLE, THE FIRE
 BARRIER SEPARATING MIXED OCCUPANCIES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT INDICATED
 IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING
 SEPARATED.
 TABLE 707.3.10 WOULD REQUIRE A 2 HOUR FIRE BARRIER WITH
 A 1 HOUR REDUCTION WITH FIRE SPRINKLERS.
  
 1ST ROUND OF COMMENTS. PLEASE SEE TABLE 508.4 OCCUPANCY
 SEPARATION, PLEASE DECLARE THE OCCUPANCY SEPARATION,
 AND IF TAKING THE REDUCTION IN HOURS FOR A FIRE
 SPRINKLERED BUILDING.
  
 3D) SEMI-COMPLIED. 2014 FBC-B 508.3.3 SEPARATION. TRUE
 SHEET 1.1 SHOWS I1 HOUR SEPARATION WITH A FIRE BARRIER
 WALL. TABLE508.3 & TABLE 707.3.10. BUT THE FLOOR PLAN
 SHEET 3.0 LIST THE SAME WALL AS A FIRE PARTITION
 (SECTION 708), NOT A FIRE BARRIER (SECTION 709).
  
  
 3E) 2ND REQUEST. THE COVERSHEET INDICATES THIS BUILDING
 TO BE FIRE SPRINKLERED. THERE IS NO FIRE SPRINKLER
 CALCULATIONS NOR PLANS IN THIS REVIEW CYCLE.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS/ BUILDING REVIEW:
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
 W. P. B. ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER
 DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH
 INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR
 MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR
 CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA
 STATUTES, MAY DESIGN A FIRE
 SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN
 THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF
 THE ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR
 DELETION OF NOT MORE THAN 49 HEADS, NOTWITHSTANDING THE
 SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM.
  
 3F) COMPLIED. STRUCTURAL STEEL FRAMING PLANS.
  
 3G) SEMI-COMPLIED. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
  
 (31)(B) WINDOWS SUBMITTED FL 14218-R8 SHEET 3 OF 17
 GLAZING DETAIL A CIRCLED NOTE THIS IS A SMALL MISSILE
 IMPACT SHEET, WINDOWS ARE LESS THAN 30 FEET ABOVE
 GRADE. THEY NEED TO BE LARGE MISSILE IMPACT RESISTANT
 RATED.
  
 (D) ROOF TOP CURBS SUBMITTED FL 16-0219.01 SEE
 TECHNICAL SHEET 5 OF 5. RESTRAINT BRACKET QUANTITY IS
 DETERMINED BY PROJECT SPECIFIC CALCULATIONS, PERFORMED
 BY A FLORIDA LICENSED PE OR FLORIDA REGISTERED
 ARCHITECT THAT CONSIDER THE UNIQUE COMBINATION OF THE
 UNIT SIZE AND APPLICABLE LATERAL AND UPLIFT PRESSURES
 FOR EACH JOB. PLEASE PROVIDE CALCULATION FOR HOW MANY
 BRACKETS WILL BE NEEDED FOR EACH TYPE OF UNIT.
  
 3H)SEMI-COMPLIED , FLORIDA APPROVAL 14218-R8 NEEDS TO
 BE CORRECTED,
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4) COMPLIED. ACCESSIBLE SHOWER.
  
 5-6) COMPLIED.
 .
 7) SHEET A3.1 FBC-B 406.8.6 AUTOMATIC SPRINKLER SYSTEM.
 A REPAIR GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.9.1.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2018-01-10 08:29:23EXIST. BLDG.
 ALT: V-B
 OCC.: B
 FULLY SPRINKLERED
 SQ. FT. 1,400
 OCC. LOAD 14
 1 RESTROOM
  
 ADDITION:
 II-B
 OCC:S-2
 FULLY SPRINKLERED
 SQ. FT. 9,906
 OCC. LOAD 33
 2 RESTROOM
  
  