Plan Review Notes
Plan Review Notes For Permit 17090202
Permit Number 17090202
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-04 17:41:451ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COVER SHEET UNDER TABLE OF CONTENTS HAS P.1-P.3
 LISTED AS ELECTRIC FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. 3.2 SHOWS THE TRANSFER SHOWER DEPTH AS 3FT 6IN
 THE INSIDE DIMENSION SHALL BE 36IN BY 36IN. PER FBC ACC
 608.2.1
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 4. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 5. SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPAY UNIT SHALL BE INSTALLED ON THE
 SIDE WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE
 LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER
 TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
  
 7. PLEASE SHOW COMPLIANCE WITH FBC ACC 610.3 IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 8. PLEASE SHOW COMPLIANCE WITH FBC ACC 602 DRINKING
 FOUNTAINS
  
 602.1 GENERAL.
 DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602.
 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 602.3 OPERABLE PARTS.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 602.5 SPOUT LOCATION.
 THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS.
  
 8. PLEASE PROVIDE SIZING CALCULATIONS FOR OIL SEPARATOR
 AND SHALL COMPLY WITH FBC PL 1003.4 /1003.4.2
  
 9. PLEASE PROVIDE MANUFACTURE SPECS FOR OIL SAND
 SEPARATOR AND THE WATTS LFMMV TEMP CONTROL VALVE. PER
 WPB AMEND TO FBC 107.2.1
  
 10. THE BRANCH DRAIN FOR THE URINAL IN BATHROOM 110
 SHALL CONNECT TO BUILDING DRAIN DOWN STREAM OF THE
 BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  