Plan Review Notes
Plan Review Notes For Permit 17090202
Permit Number 17090202
Review Stop M
Sequence Number 1
Notes
Date Text
2017-09-22 15:18:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090202
 9/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1 & M2: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE MAINTENANCE GARAGE, THE PARKING GARAGE, AND THE
 SERVICE GARAGE- SEE TABLE 403.3 AND SECTION 404.1.
  
 2) M1: REFER TO SECTION 404.1 AND CORRECT THE NOTE AND
 SEQUENCE OF OPERATION FOR EF- 5, 6, & 7.
 404.1 ENCLOSED PARKING GARAGES.
 MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING
 GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN
 ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH.
 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR
 THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC
 DETECTION DEVICES.
 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS
 APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS.
 SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH
 THEIR MANUFACTURERS? RECOMMENDATIONS.
  
 3) M1 & M2: VERIFY THAT EXHAUST FANS EF-4 & 8 WILL BE
 LOCATED A MINIMUM OF 10' ABOVE FINISHED GRADE- SECTION
 501.3.1.
  
 4) M2: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE 5-TON RTU PER SECTION 606.2.1. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THE UNIT IS NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 5) M2: VERIFY THE LOCATION OF THE NEW RTU IS NOT
 LOCATED WITHIN 10' OF THE ROOF EDGE OR PROVIDE A 42"
 HIGH GUARD OR PARAPET- SECTION 304.11.
  
 6) A PERMANENT LADDER IS REQUIRED TO ACCESS THE NEW RTU
 IN COMPLIANCE WITH SECTION 306.5. PLEASE REVISE THE
 PLANS TO SHOW THE LOCATION OF THE LADDER AND
 CONSTRUCTION DETAILS.
  
 7) M2: SUBMIT THE ROOF CURB NOA #16-0219.01 AND PROVIDE
 STRUCTURAL DETAILS FOR THE RTU ROOF OPENING- SECTION
 301.15.
  
 8) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI DADE NOA FOR
 THE NEW LOUVERS- RULE 9N-3 FAC.
  
 9) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR ALL
 MECHANICAL EQUIPMENT ASSOCIATED WITH THE CAR LIFT. SHOW
 THE LOCATIONS OF HYDRAULIC LINES AND PROVIDE
 SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  