| 2017-09-22 15:18:50 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17090202 |
| | 9/22/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M1 & M2: PROVIDE EXHAUST VENTILATION CALCULATIONS |
| | FOR THE MAINTENANCE GARAGE, THE PARKING GARAGE, AND THE |
| | SERVICE GARAGE- SEE TABLE 403.3 AND SECTION 404.1. |
| | |
| | 2) M1: REFER TO SECTION 404.1 AND CORRECT THE NOTE AND |
| | SEQUENCE OF OPERATION FOR EF- 5, 6, & 7. |
| | 404.1 ENCLOSED PARKING GARAGES. |
| | MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING |
| | GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN |
| | ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH. |
| | 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR |
| | THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC |
| | DETECTION DEVICES. |
| | 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE |
| | AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS |
| | APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS. |
| | SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | THEIR MANUFACTURERS? RECOMMENDATIONS. |
| | |
| | 3) M1 & M2: VERIFY THAT EXHAUST FANS EF-4 & 8 WILL BE |
| | LOCATED A MINIMUM OF 10' ABOVE FINISHED GRADE- SECTION |
| | 501.3.1. |
| | |
| | 4) M2: A SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR |
| | SYSTEM OF THE 5-TON RTU PER SECTION 606.2.1. PLEASE |
| | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE UNIT IS NOT |
| | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 5) M2: VERIFY THE LOCATION OF THE NEW RTU IS NOT |
| | LOCATED WITHIN 10' OF THE ROOF EDGE OR PROVIDE A 42" |
| | HIGH GUARD OR PARAPET- SECTION 304.11. |
| | |
| | 6) A PERMANENT LADDER IS REQUIRED TO ACCESS THE NEW RTU |
| | IN COMPLIANCE WITH SECTION 306.5. PLEASE REVISE THE |
| | PLANS TO SHOW THE LOCATION OF THE LADDER AND |
| | CONSTRUCTION DETAILS. |
| | |
| | 7) M2: SUBMIT THE ROOF CURB NOA #16-0219.01 AND PROVIDE |
| | STRUCTURAL DETAILS FOR THE RTU ROOF OPENING- SECTION |
| | 301.15. |
| | |
| | 8) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI DADE NOA FOR |
| | THE NEW LOUVERS- RULE 9N-3 FAC. |
| | |
| | 9) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | MECHANICAL EQUIPMENT ASSOCIATED WITH THE CAR LIFT. SHOW |
| | THE LOCATIONS OF HYDRAULIC LINES AND PROVIDE |
| | SPECIFICATIONS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |