2017-09-17 21:36:02PERMIT # 17090202
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES).
  
 2. PER NFPA 88A, CHAPTER 6: 6.3 - ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 300 L/MIN PER M2 OF
 FLOOR AREA (1 CU. FT/MIN PER SQ FT OF
 FLOOR AREA).....
  
 3. MECHANICAL VENTILATING SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 90A.
  
 4. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PLEASE PROVIDE THE
 ENGINEEREED FIRE SPRINKLER CONSTRUCTION DOCUMENTS
 COMPLYING WITH THE REQUIREMENTS OF FLORIDA STATUTE 61G.
  