2017-10-03 11:35:082014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090202
 ADD: 1422 OKEECHOBEE RD.
 CONT: CEDARS ELECTRO-MECHANICAL, INC.
 TEL: 561-588-4088 IBRAHIM CHALHOUB
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 03/2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY WITH THE LOCATION OF THE
 EXISTING BUILDING AND NEW PROPOSED ADDITION AND PROVIDE
 THE DISTANCES TO THE PROPERTY LINE. THE COVERSHEET
 STATES THE FIRE RESISTANCE REQUIREMENTS PER FBC-B TABLE
 601. A SURVEY WILL PROVIDE THE DISTANCE FROM THE
 BUILDING AND WHAT THE FIRE RESISTANCE RATING FOR
 EXTERIOR WALLS BASED ON THE FIRE SEPARATION DISTANCE
 PER TABLE 602 OF THE 2014 FBC-B.
  
 2) 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. PLEASE
 PROVIDE A SOILS REPORT FOR THE LOAD BEARING CAPACITY OF
 THE SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3) THE COVERSHEET:
 3A) THE COVERSHEET INDICATES THE COMPLIANCE WITH THE
 2014 EXISTING BUILDING CODE FOR THE NEW ADDITION
 COMPLIANCE WILL NEED TO BE MET IN CHAPTER 11, FOR THE
 EXISTING BUILDING PLEASE PROVIDE WHAT LEVEL ALTERATION
 OR PROVIDE OTHER DESIGN CRITERIA.
 2014 EXISTING BUILDING CODE 301.1. APPLICATION OF A
 METHOD SHALL BE THE SOLE BASIS FOR ASSESSING THE
 COMPLIANCE OF WORK PERFORMED UNDER A SINGLE PERMIT
 UNLESS OTHERWISE APPROVED BY THE CODE OFFICIAL.
 SECTIONS 301.1.1 THROUGH 301.1.3
  
 3B) THE PLANS INDICATE THIS BUILDING IS A S2 OCCUPANCY.
 THE COVERSHEET LIST THE S2 OCCUPANCY OF 9906 SQ. FT.
 AND THE BUSINESS OCCUPANCY 1400 SQ. FT. A TOTAL OF
 11,306 SQ. FT. THE BUSINESS OCCUPANCY BEING 1400 SQ.
 FT. IS 0.12 % OR OVER 10% BUILDING AREA MAKING THE
 BUILDING A MIXED USE BUILDING, SEE FBC-B 508.2.1.
  
 3C) PLEASE SEE TABLE 508.4 OCCUPANCY SEPARATION, PLEASE
 DECLARE THE OCCUPANCY SEPARATION, AND IF TAKING THE
 REDUCTION IN HOURS FOR A FIRE SPRINKLERED BUILDING.
  
 3D) PLEASE ALSO REVIEW AND DECLARE:
 2014 FBC-B 508.3 NONSEPARATED OCCUPANCIES.
 2014 FBC-B 508.3.3 SEPARATION.
  
 3E) THE COVERSHEET INDICATES THIS BUILDING TO BE FIRE
 SPRINKLERED. THERE IS NO FIRE SPRINKLER CALCULATIONS
 NOR PLANS IN THIS REVIEW CYCLE.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS/ BUILDING REVIEW:
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
 W. P. B. ADMINISTRATIVE CODE105.3.1.2(2) FIRE SPRINKLER
 DOCUMENTS FOR ANY NEW BUILDING OR ADDITION WHICH
 INCLUDES A FIRE SPRINKLER SYSTEM WHICH CONTAINS 50 OR
 MORE SPRINKLER HEADS. A CONTRACTOR I, CONTRACTOR II OR
 CONTRACTOR IV, CERTIFIED UNDER SECTION 633.521, FLORIDA
 STATUTES, MAY DESIGN A FIRE
 SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN
 THE ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF
 THE ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR
 DELETION OF NOT MORE THAN 49 HEADS, NOTWITHSTANDING THE
 SIZE OF THE EXISTING FIRE SPRINKLER SYSTEM.
  
 3F) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS/ BUILDING REVIEW:
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 WALL SYSTEMS
 ROOF SYSTEMS
 BUILDING ENVELOPE (PRODUCT APPROVALS) PLEASE NOTE ONLY
 (1) SET OF COVERSHEETS FOR PRODUCT APPROVALS WAS
 SUBMITTED. THERE WERE NO TECHNICAL SHEETS PROVIDED. FOR
 THE APPROVAL FROM THE DESIGN PROFESSIONAL TO BE VALID
 THE DESIGN PROFESSIONAL WILL NEED TO PROVIDE THE
 SUB-SYSTEM FOR BOTH THE ROOF & WALL PANELS, TYPE OF
 FASTENERS, SPACING OF THE GURTS AND PURLINS FOR NOT
 ONLY THE INTERIOR WALL AND ROOF FRAMING BUT FOR ALSO
 ROOF ZONES 2 & 3 AND WALL ZONE # 5. THE DESIGN
 PROFESSIONAL WOULD NEED TO KNOW IF THE STEEL BUILDING
 ENGINEER HAS TAKEN THE REDUCTIONS ALLOWABLE BY AISI
 S100/ S210 UNDER D6.2.1A FOR STRENGTH (RESISTANCE) OF
 STANDING SEAM ROOF PANEL SYSTEMS AND MEETING THE (7)
 REQUIREMENTS UNDER THIS SECTION. 2014 FBC-B 2211.4
 WALLS & 2211.5 ROOF SYSTEMS.
 THE STEEL FRAMEWORK FOR THE WALLS AND ROOF FRAMING
 MEMBERS HAS NOT BEEN SUBMITTED NOR THE SECONDARY
 FRAMING MEMBERS GIRTS OR PURLINS. THE PRESSURES FOR
 COMPONENTS AND CLADDING WALLS & ROOFS CAN NOT BE
 VERIFIED.
  
 3G) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 3H) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4) SHEET A3.2 INDICATES A BATHROOM IN THE PARKING
 GARAGE PORTION OF THE EXISTING BUILDING WITH A SHOWER.
 SHEET 3.3 SHOWS AN ENLARGED DETAIL OF THE SAME BATHROOM
 AND HANDICAPPED SHOWER. PLEASE NOTE THE SHOWER IS NOT
 DIMENSIONED. SHOW COMPLIANCE WITH;
 4A) 2014 ACCESSIBILITY CODE 608.2.1 TRANSFER TYPE
 SHOWER COMPARTMENTS. TRANSFER TYPE SHOWER COMPARTMENTS
 SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH WIDE MINIMUM ENTRY ON THE FACE OF
 THE SHOWER COMPARTMENT.
  
 4B) 2014 ACCESSIBILITY CODE FIGURE 608.2.1 TRANSFER
 TYPE SHOWER COMPARTMENTS. CLEARANCE OF 36 INCHES (915
 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED. THE
 WHEELCHAIR WILL BE 1?-0? BEHIND THE WALL WITH SEAT SO
 THE OCCUPANT AND SLIDE/ TRANSFER ON TO THE SHOWER SEAT.
  
 5) SHEET A3.1 SHOWS A MAINTENANCE GARAGE PLEASE PROVIDE
 HOW COMPLIANCE WITH: 406.8.3 FLOOR SURFACE.
 REPAIR GARAGE FLOORS SHALL BE OF CONCRETE OR SIMILAR
 NONCOMBUSTIBLE AND NONABSORBENT MATERIALS.
 EXCEPTION: SLIP-RESISTANT, NONABSORBENT, INTERIOR FLOOR
 FINISHES HAVING A CRITICAL RADIANT FLUX NOT MORE THAN
 0.45 W/CM2, AS DETERMINED BY NFPA 253, SHALL BE
 PERMITTED.
  
 6) SHEET A3.1 SHOW COMPLIANCE WITH: FBC-B 406.8.4
 HEATING EQUIPMENT. HEATING EQUIPMENT SHALL BE INSTALLED
 IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 7) SHEET A3.1 FBC-B 406.8.6 AUTOMATIC SPRINKLER SYSTEM.
 A REPAIR GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.9.1.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  