Plan Review Notes
Plan Review Notes For Permit 17090201
Permit Number 17090201
Review Stop P
Sequence Number 3
Notes
Date Text
2018-02-27 14:52:333RD REVIEW: FBC 2014 5TH EDITION
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
 1. SHT. P-904 PLEASE LABEL ALL THE FIXTURES ON THE
 ISOMETRIC DRAWING AND PROVIDE A PLUMBING FIXTURE
 SCHEDULE. PER WPB AMEND TO FBC 107.2.1. NOT ALL OF THE
 FIXTURES HAVE BEEN LABELED SUCH AS THE KITCHEN AREA AND
 FUTURE LAUNDRY, BAR AREA PLEASE CLARIFY.
  
 3. PLEASE LABEL SEPARATELY ALL THE STACKS AND RISERS ON
 THE ISOMETRIC DRAWING TO MATCH THE FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1 ALL THE STACKS ARE LABELED THE
 SAME BY THE NUMBER FROM THE KEYED NOTES PLEASE PROVIDE
 AN INDIVIDUAL LABEL OR TAG FOR EACH STACK TO COINCIDE
 WITH THE SAME TAG ON THE FLOOR PLAN.
  
 9. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FROM
 SCHIER FOR THE GREASE AND OIL/SAND INTERCEPTORS. PER
 WPB AMEND TO FBC 107.2.1 THE CALCULATIONS FROM SCHIER
 WERE NOT PROVIDED
  
 10. TWO WAY CLEAN OUTS ARE REQUIRED BETWEEN EACH
 INTERCEPTOR AND A TEST PORT ON THE DISCHARGE SIDE OF
 THE LAST INTERCEPTOR. PER WPB UTILITIES GREASE TRAP
 DETAILS FOUND IN THE FORM ON THE WPB WEBSITE UNDER
 DEVELOPMENT SERVICES. THE CLEAN OUTS SHOWN ON THE PLAN
 ARE ONE WAY CLEAN OUTS AND DO NOT COMPLY. A NOTE ON THE
 PLAN STATING TWO WAY CLEAN OUTS ARE REQUIRED BETWEEN
 EACH INTERCEPTOR WILL SUFFICE.
  
 NEW COMMENTS:
  
 1. THE ONLY SHEETS THAT WE NEED FOR THE FOUNDATION
 PERMIT ARE THE CORRECTED P-002, P-102 AND P-906 ALL
 OTHER SHEETS SHALL BE REMOVED FROM THIS PLAN SET AND
 WILL BE APPROVED UNDER MAIN PERMIT. PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHT. P-904 NOTE #3 LIST A 10? STORM DRAIN PIPE AT
 16,300 SQFT THE ISOMETRIC SHOWS A 10? STORM PIPE AT
 18,250 SQFT WHICH IS UNDERSIZED PLEASE CLARIFY. PER FBC
 PL TABLE 1106.3
  
 3. SHT. P- 904 THE FIRST SECTION OF THE HORIZONTAL
 STORM PIPING AT 10? 18,250 IS UNDERSIZED THE 8? AT
 10050SQFT IS UNDERSIZED, THERE ARE MULTIPLE SECTIONS OF
 THE STORM ISOMETRIC THAT ARE UNDERSIZED PLEASE REVIEW
 ISOMETRIC AND CHECK THE SIZING PER FBC PL TABLE 1106.3
  
 4. SHT. P- 904 SOME OF THE SECTIONS OF THE SANITARY
 ISOMETRIC DO NOT SHOW SIZE PLEASE SHOW SIZE ON ALL
 SECTIONS OF PIPING. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P- 904 SEVERAL SECTIONS OF THE HORIZONTAL
 BUILDING DRAIN AND BRANCHES ARE UNDERSIZED PLEASE SEE
 COMMENTS FOR SHT P-906 PLEASE CORRECT ON MAIN PERMIT
 SET. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT P-906+904 THE AREA DRAINS IN INDOOR /OUTDOOR
 CAF? ARE NOT VENTED. PER FBC PL 901.2.1
  
 7. SHT. P-906 THE FOLLOWING SECTIONS OF THE HORIZONTAL
 BUILDING DRAIN ARE UNDERSIZED PER FBC PL TABLE 710.1(1)
  
 A) THE 4? SECTION BETWEEN X41, X43 ANDX37, X34 IS
 UNDERSIZED IT SHOWS 214DFU THE MAX FOR 4? AT 1/8FT IS
 180DFU UPSIZE TO 6?
  
 B) THE NEXT SECTION UPSTREAM OF X32,34 SHOWS 4? 275DFU
 THE MAX FOR 4? AT 1/8FT IS 180DFU UPSIZE TO 6?
  
 C) THE NEXT SECTION UPSTREAM OF X33,35 IS NOT SIZED IT
 SHOULD BE 6?335DFU
  
 D) THE NEXT SECTION UPSTREAM OF X21,23 SHOWS 6? 820DFU
 THE MAX OF 6? AT 1/8FT IS 700DFU UPSIZE TO 8?
  
 E) THE NEXT SECTION DOWN STREAM OF X21,23 SHOWS
 6?885DFU THE MAX OF 6? AT 1/8FT IS 700DFU UPSIZE TO 8?
  
 F) THE 4? BUILDING DRAIN BRANCH UPSTREAM OF X13,15
 SHOWS 4? 250DFU THE MAX FOR 4? AT 1/8FT IS 180DFU
 UPSIZE TO 6?
  
 8. SIZE ALL FIXTURE BRANCHES SOME ARE NOT SIZED. PER
 WPB AMEND TO FBC 107.2.1
  
 9. SHT. P-906 PROVIDE UNDERGROUND STORM PIPING
 ISOMETRIC SEE COMMENTS #2,3 AND CORRECT SIZING FOR NEW
 DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  