| 2018-02-22 08:45:03 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P-904 PLEASE LABEL ALL THE FIXTURES ON THE |
| | ISOMETRIC DRAWING AND PROVIDE A PLUMBING FIXTURE |
| | SCHEDULE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. ON THE ISOMETRIC DRAWINGS FOR THE FOUNDATION PERMIT |
| | PLEASE ONLY SHOW THE PIPING THAT IS BEING RUN UNDER THE |
| | SLAB ON THE GROUND LEVEL. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE LABEL SEPARATELY ALL THE STACKS AND RISERS ON |
| | THE ISOMETRIC DRAWING TO MATCH THE FLOOR PLAN. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. ALL THE PLUMBING SHEETS SHALL BE IN ORDER SOME OF |
| | THE SHEETS WERE OUT OF ORDER IN THE PLAN SET. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. WILL THE AREA DRAIN IN THE INDOOR /OUTDOOR CAF? |
| | TERRACE BE RECEIVING STORM WATER IF SO THEY SHALL |
| | CONNECT TO THE STORM SYSTEM NOT THE SANITARY. PER WPB |
| | CODE OF ORDINANCES SEC. 90-126(5) STORM WATER, SURFACE |
| | WATER, GROUNDWATER, ARTESIAN WELL WATER, ROOF RUNOFF, |
| | SUBSURFACE DRAINAGE, SWIMMING POOL DISCHARGES, |
| | UNCONTAMINATED COOLING WATER, UNPOLLUTED INDUSTRIAL |
| | PROCESS WATERS, AIR CONDITIONING CONDENSATE, UNLESS |
| | SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING. |
| | |
| | 6. THE FLOOR DRAIN IN THE FIRE PUMP ROOM ARE NOT VENTED |
| | THEY SHALL COMPLY WITH. FBC PL 901.2.1 |
| | |
| | 7. PLEASE INDICATE THE SLOPE OF THE SANITARY AND STORM |
| | PIPING. THE SANITARY IF RAN AT THE MIN OF 1/8 FT. SOME |
| | OF THE 4? HORIZONTAL BUILDING DRAIN IS UNDERSIZED. PER |
| | FBC PL SEC 710.1 AND TABLE 710.1(1) |
| | |
| | 8. THE TROUGH DRAINS IN THE LOADING DOCK SHALL |
| | DISCHARGE THROUGH AN OIL/ SAND SEPARATOR AND ALL |
| | ELEVATOR SUMP PUMPS. PER. FBC PL 1003.4 |
| | |
| | 9. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FROM |
| | SCHIER FOR THE GREASE AND OIL/SAND INTERCEPTORS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. TWO WAY CLEAN OUTS ARE REQUIRED BETWEEN EACH |
| | INTERCEPTOR AND A TEST PORT ON THE DISCHARGE SIDE OF |
| | THE LAST INTERCEPTOR. PER WPB UTILITIES GREASE TRAP |
| | DETAILS FOUND IN THE FORM ON THE WPB WEBSITE UNDER |
| | DEVELOPMENT SERVICES. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |