| 2018-02-27 13:45:09 | RECEIVED CORRECTIONS AND APPROVED FOR FOUNDATION ONLY. |
| | |
| | |
| 2018-02-14 15:42:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | THIS REVIEW FOR FOUNDATION PERMIT ONLY. |
| | |
| | 1. PLAN DOES NOT SHOW ADDRESS OF PROJECT. PROVIDE |
| | ADDRESS ON PLAN SHEETS. FBC 107.2.1 |
| | 2. DIAGRAM FOR SERVICE DISCONNECT 2 OF 2 IS CONFUSING |
| | AND NEEDS CLARIFICATION. THIS IS LABELED AS A FIRE PUMP |
| | ATS, BUT IS SHOWS AS A DISCONNECT. THERE APPEARS TO BE |
| | A FEED FROM THE GENERATOR WHICH SHOWS TWO 600 AMP |
| | BREAKERS TIED TOGETHER, ONE FOR FIRE PUMP AND ONE FOR |
| | ATS-E. FEED FOR FIRE PUMP NEEDS TO BE INDEPENDENT OF |
| | ANY OTHER LOADS. FIRE PUMP AND JOCKEY PUMP ARE NOT |
| | SHOWN ON RISER DIAGRAM. PROVIDE CORRECTION AND |
| | CLARIFICATION. FBC 107.2.1; NEC 695.4, 695.6 |
| | 3. JOCKEY PUMP IS SHOWN AS BEING FED FROM PANEL EH1, |
| | CIRCUIT 7, 9, 11. JOCKEY PUMP FEED SHOULD NOT COME FROM |
| | A SOURCE THAT FEEDS LOADS OTHER THAN FIRE PUMP |
| | ASSOCIATED EQUIPMENT. PROVIDE CORRECTION. NEC 695.6 |
| | 4. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE PUMP |
| | MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND |
| | AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3, |
| | 695.4, 695.6 |
| | 5. LOAD CALCULATION CONCERNS HAVE BEEN DOCUMENTED FOR |
| | MAIN PERMIT #17110874 AND THIS COULD AFFECT THE NUMBER |
| | OF CONDUITS FOR THE FOUNDATION PERMIT. PROVIDE ACCURATE |
| | LOAD CALCULATION FOR EACH SERVICE. LOAD CALCULATION |
| | PROVIDED SHOWS DEMAND FACTORS APPLIED TWICE, ONCE FOR |
| | EACH PANEL, AND THEN AGAIN FOR NUMBER OF UNITS. DEMAND |
| | FACTORS CAN ONLY BE APPLIED ONCE FOR SERVICE. |
| | ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN NEC |
| | 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS A |
| | UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING, |
| | SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST |
| | ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND |
| | FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION |
| | PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100, |
| | 220; FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |