2018-02-27 13:45:09RECEIVED CORRECTIONS AND APPROVED FOR FOUNDATION ONLY.
  
  
2018-02-14 15:42:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THIS REVIEW FOR FOUNDATION PERMIT ONLY.
  
 1. PLAN DOES NOT SHOW ADDRESS OF PROJECT. PROVIDE
 ADDRESS ON PLAN SHEETS. FBC 107.2.1
 2. DIAGRAM FOR SERVICE DISCONNECT 2 OF 2 IS CONFUSING
 AND NEEDS CLARIFICATION. THIS IS LABELED AS A FIRE PUMP
 ATS, BUT IS SHOWS AS A DISCONNECT. THERE APPEARS TO BE
 A FEED FROM THE GENERATOR WHICH SHOWS TWO 600 AMP
 BREAKERS TIED TOGETHER, ONE FOR FIRE PUMP AND ONE FOR
 ATS-E. FEED FOR FIRE PUMP NEEDS TO BE INDEPENDENT OF
 ANY OTHER LOADS. FIRE PUMP AND JOCKEY PUMP ARE NOT
 SHOWN ON RISER DIAGRAM. PROVIDE CORRECTION AND
 CLARIFICATION. FBC 107.2.1; NEC 695.4, 695.6
 3. JOCKEY PUMP IS SHOWN AS BEING FED FROM PANEL EH1,
 CIRCUIT 7, 9, 11. JOCKEY PUMP FEED SHOULD NOT COME FROM
 A SOURCE THAT FEEDS LOADS OTHER THAN FIRE PUMP
 ASSOCIATED EQUIPMENT. PROVIDE CORRECTION. NEC 695.6
 4. PROVIDE SPECS OF FIRE PUMP CONTROLLER/ATS, FIRE PUMP
 MOTOR, AND JOCKEY PUMP. INCLUDE MOTOR SIZES AND
 AMPERAGE DRAW TO CONFIRM CONDUCTOR SIZING. NEC 110.3,
 695.4, 695.6
 5. LOAD CALCULATION CONCERNS HAVE BEEN DOCUMENTED FOR
 MAIN PERMIT #17110874 AND THIS COULD AFFECT THE NUMBER
 OF CONDUITS FOR THE FOUNDATION PERMIT. PROVIDE ACCURATE
 LOAD CALCULATION FOR EACH SERVICE. LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS APPLIED TWICE, ONCE FOR
 EACH PANEL, AND THEN AGAIN FOR NUMBER OF UNITS. DEMAND
 FACTORS CAN ONLY BE APPLIED ONCE FOR SERVICE.
 ADDITIONALLY, THE DEMAND FACTORS PERMITTED IN NEC
 220.84 APPLY TO DWELLING UNITS, WHICH IS DEFINED AS A
 UNIT THAT HAS PERMANENT PROVISIONS FOR LIVING,
 SLEEPING, COOKING, AND SANITATION. MANY OF THE GUEST
 ROOMS DO NOT FIT THIS DEFINITION, THEREFORE, THE DEMAND
 FACTORS COULD NOT BE APPLIED. NO LOAD CALCULATION
 PROVIDED FOR SERVICE 2 OF 2, OR FOR GENERATOR. NEC 100,
 220; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER