| 2018-02-15 10:21:37 | ****PLAN REVIEW COMMENTS**** |
| | |
| | PERMIT APPLICATION 17090201 |
| | ART LANGE BUILDING PLANS EXAMINER |
| | 561-805-6667 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| | RESIDENTIAL CODE 2015 5TH EDITION |
| | |
| | 2ND REVIEW |
| | DATE: FEBRUARY 15, 2018 |
| | ACTION: DENIED |
| | |
| | 1. ADDRESSED |
| | |
| | 2. WILL BE A PROVISO WHEN ISSUED: |
| | FLOOD ZONE CERTIFICATES |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| | |
| | 3. NOT ADDRESSED |
| | SUPPORTING DOCUMENTS SUBMITTED FROM ARDAMAN @ |
| | ASSOCIATED SHALL BE REVIEWED BY THE ARCHITECT OF RECORD |
| | AND STAMPED AS REVIEWED AND APPROVED. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 4. PARTIALLY ADDRESSED. EMAILED ANDREW SULLIVAN THE |
| | MOST RECENT VERSION OF THE THRESHOLD INSPECTOR |
| | AGREEMENT. 2/15/18. REQUESTED THAT PAGES 6,7 AND 8 BE |
| | COMPLETED AND ADDED TO THE SUPPORTING DOCUMENTS. |
| | A) INCLUDE PROJECT ADDRESS AS 251 NARCISSUS AVE |
| | B) COMPLETE CONTRACTOR AND OWNERS INFORMATION THAT WAS |
| | NOT PROVIDED. |
| | |
| | 4A. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 4B. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 4C. FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 5. ADDRESSED |
| | |
| | 6. ADDRESSED |
| | |
| | 7. ADDRESSED |
| | |
| | 8. ADDRESSED |
| | |
| | 9. ADDRESSED |
| | |
| | 10. ADDRESSED |
| | |
| | 11. ADDRESSED |
| | |
| | 12. ADDRESSED |
| | |
| | 13. NOT USED AS AN ALTERNATIVE, ADDRESSED TO DATE WE |
| | HAVE NO COMPANY SIGNED ON TO OVERSEE THE AUGER CAST |
| | PILE OR TEST PILE. FBC-B 1803.4 QUALIFIED |
| | REPRESENTATIVE. 2010 FLORIDA BUILDING CODE W * 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION SECTION 117 TESTS. THE |
| | BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS AS |
| | PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE AT |
| | THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED |
| | TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | 13A. NOT USED AS AN ALTERNATIVE, ADDRESSED SHOW HOW THE |
| | RECOMMENDATIONS FROM THE SUBSURFACE EXPLORATION AND |
| | GEOTECHNICAL ENGINEERING EVALUATION RECOMMENDATIONS |
| | WILL BE MET. FOR EXAMPLE 8.1.2 WILL SHEET PILE BE USED |
| | ON THE WEST EDGE OF THE HELEN WILKES SITE OR ALONG |
| | OLIVE AVE AND 2ND STREET. WILL COMPRESSION/ TENSION |
| | PILES BE USED TO SUPPORT THE SUPERSTRUCTURE? SHOW |
| | DETAILS ON PLANS HOW THIS WILL BE ACHIEVED. |
| | |
| | 14. ADDRESSED |
| | |
| | 15. ADDRESSED |
| | |
| | 16. ADDRESSED |
| | |
| | 17. ADDRESSED |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | |