| Plan Review Notes For Permit 17090201 |
| Permit Number |
17090201 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-09-25 12:55:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | THIS REVIEW FOR FOUNDATION PERMIT ONLY. | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, WIRE AND BREAKER SIZES FOR SERVICE. | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. INCLUDE DETAIL OF THE SECOND | | | RELIABLE POWER SOURCE FOR THE FIRE PUMP REQUIRED. NEC | | | 215.5, 230, 250.50, 250.94, 408.30, 695.3; FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|