| 2018-02-21 12:35:47 | RISER PROVIDED, CHANGED RESULT TO PASS. |
| 2018-02-12 12:34:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | |
| | THIS REVIEW FOR FOUNDATION PERMIT ONLY. |
| | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, WIRE AND BREAKER SIZES FOR SERVICE. |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. INCLUDE DETAIL OF THE SECOND |
| | RELIABLE POWER SOURCE FOR THE FIRE PUMP REQUIRED. NEC |
| | 215.5, 230, 250.50, 250.94, 408.30, 695.3; FBC 107.2.1 |
| | (YOUR RESPONSE TO THIS COMMENT STATES THAT I SHOULD SEE |
| | THE MAIN BUILDING PERMIT PLANS. AT THE TIME THIS REVIEW |
| | WAS COMPLETED, 9/25/17, THE MAIN BUILDING PLANS HAD NOT |
| | BEEN REVIEWED. THEY WERE NOT COMPLETED UNTIL 12/6/17. |
| | THEREFORE, MUCH OF THIS INFORMATION WAS NOT KNOWN. |
| | REGARDLESS, FOR A FOUNDATION PERMIT, THE RISER DIAGRAM |
| | SHEETS ARE REQUIRED AS A MATTER OF PUBLIC RECORD. |
| | SUBMIT ANY SHEETS THAT SHOW THE RISER DIAGRAM WITH |
| | DETAILS OF UNDERGROUND FEEDS AND GROUNDING FOR THE |
| | FOUNDATION.) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |