| Date |
Text |
| 2018-02-14 13:39:33 | ****CORRECTIONS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 2/26/18 NEW COMMENT: |
| | |
| | THRESHOLD |
| | |
| | THRESHOLD BUILDINGS |
| | |
| | 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND |
| | SUBMITTED IN TRIPLICATE. |
| | 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468 |
| | INSPECTOR). |
| | 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY |
| | CONTRACTOR. |
| | 4. PROVIDE STRUCTURAL INSPECTION PLAN. |
| | 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD |
| | BUILDING F.S. 553.71 (12) |
| | |
| | ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO |
| | A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER |
| | OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT. |
| | |
| | 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S. |
| | 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE |
| | FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND |
| | RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN |
| | CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY |
| | BE ISSUED. |
| | |
| | 5C) MISSING STATEMENT. THRESHOLD BUILDING, REQUIRED. |
| | W.P.B. AMENDMENT 110.3.7.4.4. ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, ?TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | F.S.? |
| | |
| | |
| | SECOND REVIEW: |
| | |
| | PARTIALLY COMPLIED: |
| | |
| | 1. ACTUAL BUILDING AREA SHOWN. INCLUDE THE BREAKDOWN OF |
| | THE ASSEMBLY OCCUPANCY. |
| | |
| | OCCUPANCY CLASSIFICATIONS, SF FOR EACH OCC CLASS, |
| | OCCUPANT LOAD PER OCCUPANCY |
| | |
| | IF ASSEMBLY OCCUPANT LOAD EXCEEDS 500 SF, THIS IS A |
| | THRESHOLD BUILDING PER FS553.71(12) AND THE STATEMENT |
| | REQUIRED BY FS553.79 IS TO BE INCLUDED ON THE PLAN. |
| | |
| | |
| | |
| | PENDING THE ABOVE ASSEMBLY CALCULATIONS |
| | |
| | 2. A RESIDENT INSPECTOR MAY BE REQUIRED, FBC 110.3.9 |
| | (IF THIS BUILDING IS NOT A THRESHOLD BUILDING). IS |
| | APPLICANT'S INTENT TO USE A RESIDENT INSPECTOR, |
| | ESPECIALLY SINCE THE OTHER TWO BUILDINGS IN THIS |
| | PROJECT REQUIRE A THRESHOLD INSPECTOR? |
| | |
| | |
| | |
| | COMPLIED WITH AN ADDITONAL NOTES. |
| | |
| | A. SIGNATURE NOT PROVIDED ON SEAL ON PAGE S0.0.1 |
| | B. ONE SET MISSING PAGE S0.0.1 |
| | |
| | |
| | FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK |
| | MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT |
| | ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | |
| | 3. S0.0.1, REVISE NOTE WHICH REFERS TO SOILS REPORT TO |
| | INCLUDE REVISION DATED 2/15/2017. |
| | |
| | |
| | |
| | NOTED, WILL BE ISSED WITH PROVISO WHEN READY. |
| | |
| | 4. THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| | |
| | THIS PARCEL IS LOCATED IN SFHA A5 WITH A BFE OF 7.0' |
| | NGVD29. PROPOSED FFE IS 9.0' NGVD29. |
| | |
| | PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION" |
| | (FORM BOARD) ELEVATION CERTIFICATE IS REQUIRED. |
| | |
| | PRIOR TO FINAL INSPECTION, A "FINISHED CONSTRUCTION" |
| | ELEVATION CERTIFICATE IS REQUIRED. THE FINISHED |
| | CONSTRUCTION ELEVATION CERTIFICATE MAY BE SENT VIA |
| | EMAIL FOR PRELIMINARY REVIEW. A SIGNED AND SEALED |
| | ORIGINAL FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | TO BE SUBMITTED AT THE BUILDING DIVISION, REVIEWED AND |
| | APPROVED PRIOR TO FINAL INSPECTION. THIS SHOULD BE DONE |
| | AS EARLY AS POSSIBLE AFTER FINAL GRADE IS COMPLETE. |
| | |