Plan Review Notes
Plan Review Notes For Permit 17090199
Permit Number 17090199
Review Stop P
Sequence Number 1
Notes
Date Text
2017-10-18 17:53:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING
 INCLUDING DFU LOAD. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 2. PROVIDE A STORM DRAIN COLLECTION ISOMETRIC DRAWING
 INCLUDING SQFT THAT IS BEING DRAINED. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 3. PLEASE PLACE NOTE ON PLAN SEPARATE PERMITS ARE
 REQUIRED FOR DOMESTIC WATER BACKFLOW AND FIRE LINE
 BACKFLOW. PER WPB UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  