| 2017-09-20 09:16:04 | 201 NORTH FLAGLER DRIVE - RESTAURANT |
| | PERMIT #17090199 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | **RETAIL/RESTAURANT FOUNDATION ONLY** |
| | |
| | FIRE PROTECTION BACKFLOW PREVENTERS: PER NFPA 24 |
| | SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE |
| | MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN |
| | BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION |
| | TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO |
| | "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION |
| | REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION |
| | TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND |
| | COMPLIANCE WITH THE FOLLOWING: |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | |