| Notes |
| Date |
Text |
| 2017-11-17 10:12:04 | FOLLOWING COMMENTS (2) ADDED TO PLAN AS PROVISO: | | | | | | 1. RISER DIAGRAM AND PANEL SCHEDULES PROVIDED SHOW THE | | | HIGH LEG ON PHASE C. HIGH LEG IS REQUIRED TO BE ON | | | PHASE B PER THE NEC. PROVIDE CORRECTION FOR RISER AND | | | PANEL SCHEDULES. NEC 408.3(E) | | | 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|