| 2017-09-14 14:13:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO ADDRESS ON THE TILTE BLOCK AND THERE IS |
| | WORDING INDICATING TEMPLE BETH EL, MARTIN COUNTY, |
| | FLORIDA. |
| | |
| | PLEASE PROVIDE THE CORRECT ADDRESS WITHIN THE TITLE |
| | BLOCK |
| | |
| | |
| | |
| | 2) THERE IS ONLY ONE SET OF PLANS SUBMITTED. |
| | |
| | PLEASE PROVIDE AT LEAST ONE ADDITIONAL SET. |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATION OF COMPLIANCE WITH ANY FIRE |
| | CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE THE APPLICABLE |
| | NOTES. |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF ANY FIRE SPRINKLER OR |
| | FIRE ALARM SYSTEMS. |
| | |
| | PLEASE PROVIDE INDICATING NOTES. |
| | |
| | ALL FIRE SPRINKLER AND FIRE ALARM WORK SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | |
| | |
| | 5) NEW DOORS ARE INDICATED; HOWEVER, THERE IS NOT DOOR |
| | SCHEDULE. |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE INCLUDING HARDWARE. |
| | |
| | |
| | |
| | 6) NEW WALLS ARE INDICATED; HOWEVER, THERE IS NO |
| | INDICATOR OF WHAT WALL TYPE IS BEING USED. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |