| 2017-09-22 15:21:18 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30; FBC 107.2.1 |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. PLAN DOES NOT SHOW ANY TYPE OF |
| | AUTOMATIC LIGHTING CONTROL REQUIRED BY THE ENERGY CODE. |
| | FBC CE 405.2.2, 405.2.2.2 |
| | 6. NOTE 12 OF GENERAL ELECTRICAL NOTES STATES THAT |
| | ROMEX MAY BE USED IN THIS INSTALLATION. PROVIDE DETAILS |
| | OF BUILDING TYPE TO COMPLY WITH PERMITTED INSTALLATIONS |
| | FOR ROMEX, OR REVISE NOTE. NEC 334.10, 12 |
| | 7. PROVIDE FIXTURE SCHEDULE AND LEGEND. FBC 107.2.1; |
| | NEC 110.3 |
| | 8. PROVIDE 2 COPIES OF PLAN FOR REVIEW, PROVIDE CORRECT |
| | ADDRESS ON PLANS FOR PROJECT, PROVIDE PROPER SIGNATURE |
| | AND SEAL PER FS 471. FS 471.003(2)(H); 471.025; FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |