| | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17090188 |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. SUITE 14D |
| | CONT: SUFFOLK |
| | TEL: 561-827-3678 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 07/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 126.36-A2.90-14D UNIT 14D: |
| | 1A) STUDY POCKET DOORS U02J. PLEASE PROVIDE WHAT TYPE |
| | OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT |
| | BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR |
| | PEOPLE THAT HAVE LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1B) MASTER BEDROOM CLOSET WITH A PAIR OF POCKET DOORS, |
| | DOORS U05AE. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL |
| | BE INSTALLED ON THE POCKET DOORS CANNOT BE FULLY |
| | RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT |
| | HAVE LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 1C) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS |
| | DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE |
| | HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE |
| | LIMITED HAND MOBILITY. |
| | 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION |
| | 100.205.(C)(2)(2).FIGURE 1( C ). |
| | |
| | 2) SHEET 242-36-A6-66-14D FLOOR FINISHES UNIT 14D: BLDG |
| | TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010) FOR |
| | TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED |
| | TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR |
| | PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF |
| | THERE IS A DROP CEILING WITH OR WITHOUT INSULATION OR |
| | PROVIDE ON SITE TESTING TO THE BELOW ASTM STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |