Plan Review Notes
Plan Review Notes For Permit 17090188
Permit Number 17090188
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-07 10:01:09 
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17090188
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE 14D
 CONT: SUFFOLK
 TEL: 561-827-3678
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 07/ 2017
 ACTION: DENIED
  
 1) SHEET 126.36-A2.90-14D UNIT 14D:
 1A) STUDY POCKET DOORS U02J. PLEASE PROVIDE WHAT TYPE
 OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT
 BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR
 PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1B) MASTER BEDROOM CLOSET WITH A PAIR OF POCKET DOORS,
 DOORS U05AE. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL
 BE INSTALLED ON THE POCKET DOORS CANNOT BE FULLY
 RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT
 HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1C) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS
 DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242-36-A6-66-14D FLOOR FINISHES UNIT 14D: BLDG
 TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010) FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION OR
 PROVIDE ON SITE TESTING TO THE BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy