| Plan Review Notes For Permit 17090153 |
| Permit Number |
17090153 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-10-10 15:17:11 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17090153 | | | 10/10/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M-1, M-2, & ST-1: THE PLANS DON'T CLEARLY | | | INDICATE HOW THE FIRE DAMPERS IN THE LOBBY AND CORRIDOR | | | WALLS WILL FUNCTION IN A FIRE OR SMOKE EVENT. PLEASE | | | INCLUDE THEIR FUNCTIONS IN THE SMOKE CONTROL SEQUENCE | | | OF OPERATION NARRATIVE ON ST-1. PLEASE NOTE THAT IF THE | | | FIRE-RATED LOBBY AND CORRIDOR WALLS ARE ALSO SMOKE | | | WALLS THEN THE DUCTS PENETRATING THE WALLS MUST BE | | | PROTECED BY FIRE/SMOKE DAMPERS ( THE CURRENT PLAN IS | | | INDICATING FIRE DAMPERS AT THE LOBBY/MECH RM WALL AND | | | THE CORRIDOR/MEN'S BATH WALL). IN ADDITION PLEASE SEE | | | SECTIONS 607.5.2 AND 607.5.7 WHICH EACH LIST EXCEPTIONS | | | FOR FIRE AND SMOKE DAMPERS FOR FOR DUCTS THAT ARE PART | | | OF A SMOKE CONTROL SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|