| 2018-03-14 16:22:51 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE VERIFICATION FROM FPU GAS UTILITIES CO. THAT |
| | THE EXISTING METER IS SIZED TO HANDLE THE NEW TOTAL BTU |
| | LOAD OF 1,687,899 BTU PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE TOTAL BTU LOAD ON THE EXISTING 2" PE PIPE IS |
| | SHOWN AT 1, 195,000 WHEN I ADDED UP THE APPLIANCES |
| | SHOWN ON THE RISER IT CAME TO 1,358,000 PLEASE CLARIFY |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PROVIDE LONGEST LENGTH FROM METER TO FURTHEST |
| | APPLIANCE WHICH IS THE FIRE PIT THE RISER IS MISSING A |
| | DIMENSION IT APPEARS TO BE ABOUT 120' PER FBC FG |
| | 402.4.1 |
| | |
| | 4. AT 120 LONGEST LENGTH THE EXISTING 2" PE PIPE IS |
| | UNDERSIZED FOR THE TOTAL BTU LOAD ON THAT PIPE PER FBC |
| | FG TABLE 402.4(21) IT SHALL BE 3" |
| | |
| | 5. THE 3/4" SCH 40 METALLIC PIPE SUPPLING THE FIRE PIT |
| | IS UNDERSIZED AT 120' LONGEST LENGTH PER FBC FG TABLE |
| | 402.4(2) IT SHOULD BE 1" |
| | |
| | 6. THE EXISTING 1/2" SCH 40 METALLIC PIPE FEEDING THE |
| | FUTURE FIRE PLACE IS UNDERSIZED AT 100' LONGEST LENGTH |
| | PER FBC FG TABLE 402.4(2) IT SHALL BE 1" |
| | |
| | 7. IN IN SEVERAL PLACES ON THE GAS RISER AND GAS FLAT |
| | DRAWING IT SHOWS THE BTU LOAD @ 200' IS THIS THE |
| | LONGEST LENGTH THAT THE SYSTEM IS BEING SIZED FROM |
| | PLEASE CLARIFY. PER FBC FG 402.4.1 AND WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |