| 2018-01-26 12:25:28 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SANITARY VENT FOR THE NEW CABANA BATHROOM AND |
| | SUMER KITCHEN SHALL NOT TERMINATE THRU THE SIDE WALL OF |
| | THE STRUCTURE. VENT TERMINALS EXTENDING THROUGH THE |
| | WALL SHALL TERMINATE AT A POINT NOT LESS THAN 10 FEET |
| | FROM A LOT LINE. SHT. ASP01.0 SHOWS THE STRUCTURE ONLY |
| | 7'-6" FROM THE PROPERTY LINE. VENT TERMINALS EXTENDING |
| | THROUGH THE WALL SHALL TERMINATE AT A POINT NOT LESS |
| | THAN 10 FEET ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS |
| | SHALL NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE |
| | WITH SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE |
| | PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR |
| | BLOCKING THE VENT OPENING. THE VENT WILL HAVE TO RUN UP |
| | THRU THE ROOF OR INTO THE ATTIC AND TIE INTO AN |
| | EXISTING VENT. PER FBC RES P3103.6 |
| | |
| | 2. THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED |
| | IN SIZE IN THE DIRECTION OF THE FLOW. THE SANITARY |
| | ISOMETRIC SHOWS THE BUILDING SEWER REDUCING IN SIZE |
| | FROM 4" TO 3" THEN BACK TO 4" BEFORE CONNECTING TO THE |
| | LIFT STATION. THE PIPING CAN BE 3" OR 4" BUT IT HAS TO |
| | REMAIN THE SAME SIZE. PER FBC RES P3005.1.7 |
| | |
| | 3. TWO WAY CLEAN OUTS ARE REQUIRED ON THE PIPING WHERE |
| | IT EXITS THE STRUCTURE AND THE OUT LET SIDE OF THE LIFT |
| | STATION. PER FBC RES P3005.2.7, P3005.2.2 |
| | |
| | 4. THE CLEAN OUT SHOWN AT THE CORNER OF BUILDING DRAIN |
| | IS SHOWN IN THE WRONG DIRECTION IT SHALL BE IN THE |
| | DIRECTION OF THE FLOW. PER FBC RES P3005.2.8 |
| | |
| | 5. THE MANUFACTURE SPECIFICATIONS FOR THE LIFT STATION |
| | SHOWN ON THE PLAN IS TO SMALL AND LIGHT TO READ PLEASE |
| | PLACE NOTE ON PLAN STATING THE MANUFACTURE |
| | SPECIFICATION SHALL BE ON JOBSITE FOR INSPECTIONS. PER |
| | WPB AMENDT TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |