2018-01-26 12:25:282ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY VENT FOR THE NEW CABANA BATHROOM AND
 SUMER KITCHEN SHALL NOT TERMINATE THRU THE SIDE WALL OF
 THE STRUCTURE. VENT TERMINALS EXTENDING THROUGH THE
 WALL SHALL TERMINATE AT A POINT NOT LESS THAN 10 FEET
 FROM A LOT LINE. SHT. ASP01.0 SHOWS THE STRUCTURE ONLY
 7'-6" FROM THE PROPERTY LINE. VENT TERMINALS EXTENDING
 THROUGH THE WALL SHALL TERMINATE AT A POINT NOT LESS
 THAN 10 FEET ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS
 SHALL NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE
 WITH SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE
 PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR
 BLOCKING THE VENT OPENING. THE VENT WILL HAVE TO RUN UP
 THRU THE ROOF OR INTO THE ATTIC AND TIE INTO AN
 EXISTING VENT. PER FBC RES P3103.6
  
 2. THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED
 IN SIZE IN THE DIRECTION OF THE FLOW. THE SANITARY
 ISOMETRIC SHOWS THE BUILDING SEWER REDUCING IN SIZE
 FROM 4" TO 3" THEN BACK TO 4" BEFORE CONNECTING TO THE
 LIFT STATION. THE PIPING CAN BE 3" OR 4" BUT IT HAS TO
 REMAIN THE SAME SIZE. PER FBC RES P3005.1.7
  
 3. TWO WAY CLEAN OUTS ARE REQUIRED ON THE PIPING WHERE
 IT EXITS THE STRUCTURE AND THE OUT LET SIDE OF THE LIFT
 STATION. PER FBC RES P3005.2.7, P3005.2.2
  
 4. THE CLEAN OUT SHOWN AT THE CORNER OF BUILDING DRAIN
 IS SHOWN IN THE WRONG DIRECTION IT SHALL BE IN THE
 DIRECTION OF THE FLOW. PER FBC RES P3005.2.8
  
 5. THE MANUFACTURE SPECIFICATIONS FOR THE LIFT STATION
 SHOWN ON THE PLAN IS TO SMALL AND LIGHT TO READ PLEASE
 PLACE NOTE ON PLAN STATING THE MANUFACTURE
 SPECIFICATION SHALL BE ON JOBSITE FOR INSPECTIONS. PER
 WPB AMENDT TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  