| 2018-01-09 09:19:56 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS |
| | REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE FOLLOWING THE PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE AND CO |
| | ALARMS. IF NONE ARE EXITSTING, OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATION. FBC RE314.3, 315.1; FBC 107.2.1 |
| | (SMOKE ALARMS WITH BATTERY POWER ARE ONLY PERMITTED FOR |
| | LEVEL 1 ALTERATIONS. PROVIDE CORRECTION TO SHOW SMOKE |
| | ALARMS FED FROM THE DWELLING ELECTRICAL SYSTEM. FBC RE |
| | 314.4) |
| | 9.CORRECTED. |
| | 10. CORRECTED. |
| | |
| | NEW COMMENT: |
| | 11. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |