Plan Review Notes
Plan Review Notes For Permit 17090137
Permit Number 17090137
Review Stop E
Sequence Number 1
Notes
Date Text
2017-09-27 13:57:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE
 FOR THE DESIGN. PROVIDE CORRECTION. FS 481.229; FBC
 107.2.1, 107.3.5
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. SEVERAL ITEMS ON PANEL SCHEDULE ARE NOT INCLUDED
 IN LOAD CALCULATION. NEC 220; FBC RE3602.3
 3. PROVIDE RATING OF METER CAN TO VERIFY THAT IT IS
 SUFFICIENTLY SIZED TO HANDLE THE ADDITIONAL LOAD. NEC
 110.3, 215.5
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 5. NOTE # 6 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER 2008 NEC 406.11. THIS IS NOT THE CURRENT
 CODE AND THIS CODE SECTION DOES NOT APPLY TO TAMPER
 RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC 406.12;
 FBC RE4002.14; FBC PREFACE
 6. PROVIDE GFCI PROTECTION FOR ALL OUTLETS WITHIN 6
 FEET OF A SINK, AND ALL EXTERIOR LOCATIONS. NEC 210.8;
 FBC RE3902.3, 3902.7
 7. LIGHTS INSTALLED WITHIN 5 FEET OF THE POOL ARE
 REQUIRED TO BE MOUNTED AT LEAST 12 FEET HIGH PER NEC
 AND FBC RE. THE LIGHTS PROPOSED AT GROUND LEVEL ARE IN
 VIOLATION OF THIS CODE. PROVIDE CORRECTION. NEC
 680.22(B)(1); FBC RE 4203.4.1
 8. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE AND CO
 ALARMS. IF NONE ARE EXITSTING, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC RE314.3, 315.1; FBC 107.2.1
 9. LIGHTING IN THE SHOWER APPEARS TO BE A RECESS LIGHT.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D);
 FBC RE4003.11
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  