| Date |
Text |
| 2017-09-27 13:57:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE |
| | FOR THE DESIGN. PROVIDE CORRECTION. FS 481.229; FBC |
| | 107.2.1, 107.3.5 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. SEVERAL ITEMS ON PANEL SCHEDULE ARE NOT INCLUDED |
| | IN LOAD CALCULATION. NEC 220; FBC RE3602.3 |
| | 3. PROVIDE RATING OF METER CAN TO VERIFY THAT IT IS |
| | SUFFICIENTLY SIZED TO HANDLE THE ADDITIONAL LOAD. NEC |
| | 110.3, 215.5 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 5. NOTE # 6 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER 2008 NEC 406.11. THIS IS NOT THE CURRENT |
| | CODE AND THIS CODE SECTION DOES NOT APPLY TO TAMPER |
| | RESISTANT RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; |
| | FBC RE4002.14; FBC PREFACE |
| | 6. PROVIDE GFCI PROTECTION FOR ALL OUTLETS WITHIN 6 |
| | FEET OF A SINK, AND ALL EXTERIOR LOCATIONS. NEC 210.8; |
| | FBC RE3902.3, 3902.7 |
| | 7. LIGHTS INSTALLED WITHIN 5 FEET OF THE POOL ARE |
| | REQUIRED TO BE MOUNTED AT LEAST 12 FEET HIGH PER NEC |
| | AND FBC RE. THE LIGHTS PROPOSED AT GROUND LEVEL ARE IN |
| | VIOLATION OF THIS CODE. PROVIDE CORRECTION. NEC |
| | 680.22(B)(1); FBC RE 4203.4.1 |
| | 8. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE AND CO |
| | ALARMS. IF NONE ARE EXITSTING, OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATION. FBC RE314.3, 315.1; FBC 107.2.1 |
| | 9. LIGHTING IN THE SHOWER APPEARS TO BE A RECESS LIGHT. |
| | LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| | FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D); |
| | FBC RE4003.11 |
| | 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC CE R404.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |