Plan Review Notes
Plan Review Notes For Permit 17090137
Permit Number 17090137
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-20 15:26:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE SOILS REPORT ISSUED BY AN ACCREDITED
 LABORATORY PER FBCR401.4.
 2. PROVIDE ENERGY SUBMITTAL PER FBCR 101.5.1.1.
 3. PALM BEACH COUNTY IMPACT FEES APPLY.
 4. ROOFING PERMIT REQUIRED.
 5. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 BBG GRILL.
 6. PROVIDE SHOP DRAWINGS FOR ENGINEERED STAIRS.
 7. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE LOCATION,
 ROUGH OPENINGS AND DESIGN WIND LOADS.
 8. REFERENCE PLAN NOTES - RAILING AND STAIR NOTES ON
 PLAN PAGE A-4.0 FOR THE FOLLOWING:
 8A. NOTE 1 - THE SFBC IS NO LONGER ENFORCED. REFERENCE
 STAIR HANDRAILS PER FBCR311.7.8 AND STAIR GUARDS PER
 FBCR 312.1.2.
 8B. NOTE 2 - CHANGE CODE REFERENCE FOR STAIR RAILS AND
 GRAB RAILS TO FBCR 311.7.8.
 8C. NOTE 3 - CHANGE CODE REFERENCE FOR GUARDS TO
 FBCR312.1.2.
 8D. NOTE 4 - CHANGE CODE REFERENCE FOR VERTICAL PICKETS
 TO FBCR 312.1.3.
 8E. NOTE 5 - CHANGE CODE REFERENCE FOR LOAD TEST TO
 ASCE7, SECTION 5.5.1.
 9. DESIGN PROFESSIONAL TO SIGN AND SEAL PLANS.
 10. NOA NO. 16-0629.10 IS EXPIRED. PROVIDE CURRENT NOA
 FOR SGD.
 11. ALL PRODUCT APPROVALS SHALL BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD.
 12. VALUE - STATED VALUE IS LOW FOR PROPOSED WORK.
  
 SOILS
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 ENERGY
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
 _ OR _
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 PALM BEACH COUNTY IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 GENERAL DESIGN INFORMATION
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 STAIRS
 R311.7 STAIRWAYS.
  
 R311.7.1 WIDTH.
 STAIRWAYS SHALL NOT BE LESS THAN 36 INCHES (914 MM) IN
 CLEAR WIDTH AT ALL POINTS ABOVE THE PERMITTED HANDRAIL
 HEIGHT AND BELOW THE REQUIRED HEADROOM HEIGHT.
 HANDRAILS SHALL NOT PROJECT MORE THAN 4.5 INCHES (114
 MM) ON EITHER SIDE OF THE STAIRWAY AND THE MINIMUM
 CLEAR WIDTH OF THE STAIRWAY AT AND BELOW THE HANDRAIL
 HEIGHT, INCLUDING TREADS AND LANDINGS, SHALL NOT BE
 LESS THAN 311/2 INCHES (787 MM) WHERE A HANDRAIL IS
 INSTALLED ON ONE SIDE AND 27 INCHES (698 MM) WHERE
 HANDRAILS ARE PROVIDED ON BOTH SIDES.
 R311.7.3 VERTICAL RISE.
 A FLIGHT OF STAIRS SHALL NOT HAVE A VERTICAL RISE
 LARGER THAN 12 FEET (3658 MM) BETWEEN FLOOR LEVELS OR
 LANDINGS.
 R311.7.5.1 RISERS.
 THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM).
 THE RISER SHALL BE MEASURED VERTICALLY BETWEEN LEADING
 EDGES OF THE ADJACENT TREADS. THE GREATEST RISER HEIGHT
 WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE
 SMALLEST BY MORE THAN 3/8 INCH (9.5 MM). RISERS SHALL
 BE VERTICAL OR SLOPED FROM THE UNDERSIDE OF THE NOSING
 OF THE TREAD ABOVE AT AN ANGLE NOT MORE THAN 30 DEGREES
 (0.51 RAD) FROM THE VERTICAL. OPEN RISERS ARE PERMITTED
 PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT
 PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM)
 SPHERE.
 R311.7.5.2 TREADS.
 THE MINIMUM TREAD DEPTH SHALL BE 10 INCHES (254 MM).
 THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY BETWEEN
 THE VERTICAL PLANES OF THE FOREMOST PROJECTION OF
 ADJACENT TREADS AND AT A RIGHT ANGLE TO THE TREAD?S
 LEADING EDGE. THE GREATEST TREAD DEPTH WITHIN ANY
 FLIGHT OF STAIRS SHALL NOT EXCEED THE SMALLEST BY MORE
 THAN 3/8 INCH (9.5 MM).
 R311.7.6 LANDINGS FOR STAIRWAYS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE MINIMUM WIDTH PERPENDICULAR TO
 THE DIRECTION OF TRAVEL SHALL BE NO LESS THAN THE WIDTH
 OF THE FLIGHT SERVED. LANDINGS OF SHAPES OTHER THAN
 SQUARE OR RECTANGULAR SHALL BE PERMITTED PROVIDED THE
 DEPTH AT THE WALK LINE AND THE TOTAL AREA IS NOT LESS
 THAN THAT OF A QUARTER CIRCLE WITH A RADIUS EQUAL TO
 THE REQUIRED LANDING WIDTH. WHERE THE STAIRWAY HAS A
 STRAIGHT RUN, THE MINIMUM DEPTH IN THE DIRECTION OF
 TRAVEL SHALL BE NOT LESS THAN 36 INCHES (914 MM).
 R311.7.8 HANDRAILS.
 HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF
 EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR
 MORE RISERS. R311.7.8.
 HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED
 PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF
 RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM)
 AND NOT MORE THAN 38 INCHES (965 MM). R311.7.8.1 HEIGHT
 R312.1.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE
 WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER.
 R311.7.9 ILLUMINATION.
 ALL STAIRS SHALL BE PROVIDED WITH ILLUMINATION IN
 ACCORDANCE WITH SECTION R303.6.
 453.8.8.6
 EXTERIOR STAIRS, BALCONIES, RAMPS, AND UPPER LEVEL
 CORRIDORS AROUND THE PERIMETER OF BUILDINGS SHOULD HAVE
 OPEN-TYPE HANDRAILS OR OTHER ARCHITECTURAL FEATURES TO
 ALLOW SURVEILLANCE.
 R311.7.10.1 SPIRAL STAIRWAYS.
 SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED THE MINIMUM
 CLEAR WIDTH AT AND BELOW THE HANDRAIL SHALL BE 26
 INCHES (660 MM) WITH EACH TREAD HAVING A 71/2-INCH (190
 MM) MINIMUM TREAD DEPTH AT 12 INCHES (914 MM) FROM THE
 NARROWER EDGE. ALL TREADS SHALL BE IDENTICAL, AND THE
 RISE SHALL BE NO MORE THAN 91/2 INCHES (241 MM). A
 MINIMUM HEADROOM OF 6 FEET 6 INCHES (1982 MM) SHALL BE
 PROVIDED.
  
 SECTION R312 GUARDS AND WINDOW FALL PROTECTION
  
 GUARDS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 R312.1.1 THROUGH R312.1.4.
 R312.1.1 WHERE REQUIRED. R312.1 GUARDS.
 FBCR312.1.1 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED
 WALKING SURFACES, INCLUDING STAIRS, RAMPS AND LANDINGS,
 THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED
 VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT
 WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF
 THE OPEN SIDE. INSECT SCREENING SHALL NOT BE CONSIDERED
 AS A GUARD.
 R312.1.2 HEIGHT.
 REQUIRED GUARDS AT OPEN-SIDED WALKING SURFACES,
 INCLUDING STAIRS, PORCHES, BALCONIES OR LANDINGS, SHALL
 BE NOT LESS THAN 36 INCHES (914 MM) HIGH MEASURED
 VERTICALLY ABOVE THE ADJACENT WALKING SURFACE, ADJACENT
 FIXED SEATING OR THE LINE CONNECTING THE LEADING EDGES
 OF THE TREADS.
  
 SECTION 1012 HANDRAILS
  
 1012.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM). HANDRAIL HEIGHT OF ALTERNATING TREAD
 DEVICES AND SHIP LADDERS, MEASURED ABOVE TREAD NOSINGS,
 SHALL BE UNIFORM, NOT LESS THAN 30 INCHES (762 MM) AND
 NOT MORE THAN 34 INCHES (864 MM).
 1012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE STAIR FLIGHTS AT STAIRWAYS AND
 THE RAMP RUNS AT RAMPS.
 1009.8 STAIRWAY LANDINGS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE WIDTH OF LANDINGS SHALL NOT BE
 LESS THAN THE WIDTH OF STAIRWAYS THEY SERVE. EVERY
 LANDING SHALL HAVE A MINIMUM WIDTH MEASURED
 PERPENDICULAR TO THE DIRECTION OF TRAVEL EQUAL TO THE
 WIDTH OF THE STAIRWAY. WHERE THE STAIRWAY HAS A
 STRAIGHT RUN THE DEPTH NEED NOT EXCEED 48 INCHES (1219
 MM). DOORS OPENING ONTO A LANDING SHALL NOT REDUCE THE
 LANDING TO LESS THAN ONE-HALF THE REQUIRED WIDTH. WHEN
 FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO A LANDING. WHEN WHEELCHAIR SPACES
 ARE REQUIRED ON THE STAIRWAY LANDING IN ACCORDANCE WITH
 SECTION 1007, THE WHEELCHAIR SPACE SHALL NOT BE LOCATED
 IN THE REQUIRED WIDTH OF THE LANDING AND DOORS SHALL
 NOT SWING OVER THE WHEELCHAIR SPACES.
 EXCEPTION: AISLE STAIRS COMPLYING WITH SECTION 1028.
  
 SECTION 1013 GUARDS
  
 1013.2 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM)
 HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL
 BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.8.
 1013.3 HEIGHT.
 REQUIRED GUARDS SHALL NOT BE LESS THAN 42 INCHES (1067
 MM) HIGH, MEASURED VERTICALLY AS FOLLOWS:
 1. FROM THE ADJACENT WALKING SURFACES;
 2. ON STAIRS, FROM THE LINE CONNECTING THE LEADING
 EDGES OF THE TREAD NOSINGS; AND
 3. ON RAMPS, FROM THE RAMP SURFACE AT THE GUARD.
 R312.1.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE
 WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER.
 1013.4 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 LOAD TEST - FBC CHPT 16
  
 1607.8 LOADS ON HANDRAILS, GUARDS, GRAB BARS, SEATS AND
 VEHICLE BARRIERS.
 HANDRAILS, GUARDS, GRAB BARS, ACCESSIBLE SEATS,
 ACCESSIBLE BENCHES AND VEHICLE BARRIERS SHALL BE
 DESIGNED AND CONSTRUCTED TO THE STRUCTURAL LOADING
 CONDITIONS SET FORTH IN THIS SECTION.
 1607.8.1 HANDRAILS AND GUARDS.
 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) (0.73
 KN/M) IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS
 HANDRAIL ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH
 SECTION 2407.
  
 DESIGN PROFESSIONAL
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 PRODUCT APPROVALS
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 VALUE
 VALUATION - BASED ON THE INTERNATIONAL CODE COUNCIL
 (ICC) BUILDING VALUATION DATA YOUR STATED VALUE APPEARS
 LOW.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 RE-SUBMITTAL
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  