| 2017-10-13 12:06:44 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17090120 |
| | 10/13/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M101 & M121.8: THE REVISED PLANS UNDER PERMIT |
| | #17080449 WERE APPROVED WITH A PROVISO THAT REVISED |
| | VENTILATION AND AIR BALANCE CALCULATIONS FOR THE |
| | ALTERED KITCHEN SYSTEMS WOULD BE PROVIDED. PLEASE |
| | PROVIDE THE CALCULATIONS AND A REVISED KITCHEN |
| | EQUIPMENT LAYOUT AND EQUIPMENT SCHEDULE. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR ALL GAS-FIRED COOKING |
| | APPLIANCES AND PROVIDE COMBUSTION AIR CALCULATIONS. |
| | PLEASE NOTE THE FOLLOWING: A) SEPARATE PERMITS ARE |
| | REQUIRED FOR HOOD EXHAUST AND FIRE SUPPRESSION SYSTEMS. |
| | B) REFER TO SECTION 508.1.1 FOR MAKEUP AIR TEMPERATURE |
| | REQUIREMENT. |
| | |
| | 2) M121.5, ITEM #3 IN THE NARRATIVE: PLEASE SHOW THE |
| | LOCATIONS OF GALLERIES 135 & 137 ON THE PLAN. |
| | |
| | 3) M121.7, ITEM #2 IN THE NARRATIVE: PLEASE SHOW THE |
| | LOCATIONS OF GALLERIES 135 & 137 ON THE PLAN. |
| | |
| | 4) M122.5: PROVIDE DUCT SIZES ON THE PLANS. |
| | |
| | 5) M122.8: THERE ARE MISSING FS DAMPER SYMBOLS FOR THE |
| | DUCTS IN THE SHAFT BY THE ELEVATOR. |
| | |
| | 6) M123.8B: IT APPEARS THE WATER HEATER FLUE AND INTAKE |
| | DUCT ARE NOW BEING ROUTED TO THE ROOF, HOWEVWER THE |
| | NOTES ON THE PLAN ARE STILL INDICATING SIDEWALL |
| | TERMINATIONS- PLEASE CORRECT. |
| | |