| 2017-09-14 11:11:07 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET M-1 THE RANGE EXHAUST HOOD IS SHOWN OVER | | | THE KITCHEN SINK. PLEASE CORRECT. FBC 107.2.1 | | | | | | 2) ON SHEET M-2 THERE IS A 12 X 12 SUPPLY THAT HAS A | | | DROP CONNECTED TO A LINEAR DIFFUSER LOCATED IN THE HALL | | | THAT IS LABELED AS A RETURN AIR GRILL. PLEASE CLARIFY. | | | ALSO, THE SIZE OF THE DROP IS NOT SPECIFIED. FBC | | | 107.2.1 | | | | | | 3) ON SHEET M-2 IN BATHROOM #2, THERE IS A 4 " SUPPLY | | | WITH A GRILL THAT IS NOT IDENTIFIED WITH A MARK, CFMS | | | OR GRILL SIZE. PLEASE CORRECT. FBC 107.2.1 | | | | | | 4) THE TOTAL OF THE CFMS LISTED ON THE PLANS FOR AHU 2 | | | AND AHU 3 ARE NOT CONSISTANT WITH THE SUPPLY AIR CFMS | | | LISTED IN THE EQUIPMENT SCHEDULE. PLEASE CORRECT. FBC-M | | | 1401 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2017-09-05 10:29:14 | REVISION ROUTED TO RMCDOUGAL |
|